24VNA6: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
A07588
Fig. 1 – Connecting Tubing Installation
The  outdoor  unit contains  the  correct  amount  of refrigerant  charge  for
operation  with AHRI  rated  and  factory-approved  smallest  indoor  unit
when connected by 15 ft (4.57 m) of field-supplied or factory accessory
tubing.
Adjust refrigerant charge by adding or removing the charge to/from the
unit  depending  on  lineset  length  and  indoor  unit  as  calculated  and
displayed on the UI. The user interface (UI) calculates required charge
adjustment and total system charge required.  For proper unit operation,
check refrigerant charge using charging information in the Check Charge
section of this instruction.
IMPORTANT:  Liquid-line  size  is  3/8-in.  OD  for  all  24VNA6
applications including long line applications.
IMPORTANT:  Always  install  the  factory-supplied  liquid-line  filter
drier. Obtain replacement filter driers from your distributor or branch.
Installation
IMPORTANT: Effective January 1, 2015, all split system and packaged
air  conditioners  must  be  installed  pursuant  to  applicable  regional
efficiency standards issued by the Department of Energy.
Specifications for this unit in residential new construction market require
the  outdoor  unit,  indoor  unit  (including  metering  device),  refrigerant
tubing sets, and filter drier, and muffler listed in pre-sale literature. There
can be no deviation. Consult the Service Manual – Air Conditioners and
Heat Pumps Using Puron Refrigerant to obtain required unit changes for
specific applications and for R-22 retrofit.
Step 1 – Check Equipment and Job Site
Unpack Unit
Move to final location. Remove carton taking care not to damage unit. 
This unit employs one louver spacer on each of the four sides to prevent
louver  movement  during  operation.    The  louver  spacers  are  trapped
between  the coil  surface and louver  at the approximate  center of  each
side (See Fig. 2).  This louver spacer should be present and, if dislodged
during shipment, must be reinstalled before unit is placed into operation.
A11380a
Fig. 2 – Louver Spacer Location
Inspect Equipment
File  claim  with  shipping  company  prior  to  installation  if  shipment  is
damaged or incomplete. Locate unit rating plate on unit corner panel. It
contains information needed to properly install unit. Check rating plate
to be sure unit matches job specifications.
Step 2 – Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie down
bolts  should  be  used  and  fastened through knockouts  provided  in  unit
base pan. Refer to unit mounting pattern in Fig. 3 to determine base pan
size and knockout hole location.
Fig. 3 – Tiedown Knockout Locations
For  hurricane  tie  downs,  contact  distributor  for  details  and  PE
(Professional Engineer) Certification, if required.
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
If  proper  lineset  routing  techniques  are  not  followed,  variable  speed
systems  can  be  susceptible  to  lineset  transmitted  noise  inside  the
dwelling and, in extreme cases, tubing breakage.
INSULATION
SUCTION TUBE
LIQUID TUBE
OUTDOOR WALL INDOOR WALL
LIQUID TUBE
SUCTION TUBE
INSULATION
CAULK
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
JOIST
1” (25.4 mm)
 MIN
THROUGH THE WALL
SUSPENSION
UNIT BASE PAN
Dimension in. (mm)
TIEDOWN KNOCKOUT LOCATIONS in. (mm)
A B C
35 X 35
(889 X 889)
9–1/8(231.8) 6–9/16 (166.7) 28–7/16 (722.3)
3/4 IN.DIA TIEDOWN
KNOCKOUTS IN BASEPAN
TWO (2) PLACES
C
B
A
VIEW FROM TOP