24VNA6: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
On rooftop  applications,  mount on  level  platform or frame.  Place  unit
above a load-bearing wall and isolate unit and tubing set from structure.
Arrange supporting  members  to  adequately support  unit  and minimize
transmission  of  vibration  to  building.  Consult  local  codes  governing
rooftop applications.
Roof mounted units  exposed  to  winds above 5  mph may require wind
baffles.  Consult  the  Service  Manual  -  Residential  Split  System  Air
Conditioners and Heat Pumps Using Puron® Refrigerant for wind baffle
construction.
NOTE: Unit must be level to within ±2° (±3/8 in./ft,±9.5 mm/m.) per
compressor manufacturer specifications.
Step 3 – Clearance Requirements
When  installing,  allow  sufficient  space  for  airflow  clearance,  wiring,
refrigerant  piping,  and  service. Allow  24  in.  (609.6  mm)  clearance  to
service  end  of  unit  and  48  in.  (1219.2  mm)  (above  unit.  For  proper
airflow, a 6-in. (152.4 mm) clearance on 1 side of unit and 12-in. (304.8
mm) on all remaining sides must be maintained. Maintain a distance of
24 in. (609.6 mm) between units.  Position so water, snow, or ice from
roof or eaves cannot fall directly on unit. 
On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof
surface. 
Step 4 – Operating Ambient
The  minimum  outdoor  operating  ambient  in  cooling  mode  is  55°F
(12.78°C)  without  low  ambient  cooling  enabled,  and  the  maximum
outdoor operating ambient in cooling mode is 125°F (51.67°C). 
Step 5 – Elevate Unit
Elevate  unit  per  local  climate  and  code  requirements  to  provide
clearance above estimated snowfall level and ensure adequate drainage
of unit.
Step 6 – In Long-Line Applications, Install Liquid-Line 
Solenoid Valve (LSV)
For refrigerant piping arrangements with equivalent lengths of  greater
than 80 ft. (24.38 m) and/or when elevation difference between indoor
and  outdoor  unit  is  greater  than  ±20  ft.  (±6.10  m),  follow  the  piping
configuration  and  liquid  line  solenoid  valve  (LSV)  accessory
requirements from the Residential Piping and Long-line guideline. CCH,
start  gear  and  piston  changes  do  not  apply.  If  required  by  Long-Line
Guideline,  install  LSV  kit,  part  no.  KHALS0401LLS.  LSV  should  be
installed within 2 ft. (0.61 m) of outdoor unit with flow arrow pointing
toward outdoor unit. 
Make the necessary electrical connections as shown in Fig. 4 and Fig. 5
and  by  following  the  Installation  Instructions  included  with  accessory
kit. 
IMPORTANT: Flow arrow must point toward outdoor unit.
A180243
Fig. 4 – Liquid Line Solenoid Electrical Connection
(Required for long line applications)
A150776
Fig. 5 – Infinity Furnace or Fan Coil Wiring with Communicating 
Variable Speed AC
Step 7 – Make Piping Connections
CAUTION
!
UNIT OPERATION HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
Do not allow water and/or ice to build up in base pan.
CAUTION
!
UNIT OPERATION HAZARD
Failure  to  follow  this  caution  may  result  in  equipment  damage  or
improper operation.
Locate  the  unit  in  such  a  way  that  it  is  stable  in  all  circumstances
including adverse weather conditions. 
WARNING
!
PERSONAL INJURY AND UNIT DAMAGE
HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve  pressure  and  recover  all  refrigerant  before  system  repair  or
final  unit  disposal.  Use  all  service  ports  and  open  all  flow-control
devices, including solenoid valves.
                      Furnace or
                      Fan Coil
Variable Speed
AC or HP
D
C
B
A
Wall Control
HP or AC
OAT
RYOWCHUM
C
Humidifier
24vac
Furnace or Fan Coil
’C’ connection optional
Sheild Cable
D not required
Unused Wires
WT
YL
GN
D
C
B
A