10
PERFORMANCE DATA
DESCRIPTION
UNIT SIZE
060---14 080---14 080---20 100---20 120---20
Certified Temp Rise Range (_F)
Low 40—70 40—70 40—70 40—70 40—70
High 35—65 40—70 35—65 45—75 45—75
Certified Ext Static Pressure (ESP) (in. wc)
Heating 0.12 0.15 0.15 0.20 0.20
Cooling 0.50 0.50 0.50 0.50 0.50
Airflow CFM*
Heating Low 670 (735{) 910 (1000{) 870 (955{) 1060 (1165{) 1345 (1480{)
Heating High 1055 1390 1500 1525 1880
Cooling (Max) 1400 1395 1990 2000 2100
Output Capacity Btuh} (ICS)
Low 37,000 50,000 50,000 63,000 75,000
High 56,000 75,000 75,000 94,000 113,000
AFUE%}
95.0 95.0 95.0 95.0 95.0
Input Btuh**
Low 39,000 52,000 52,000 65,000 78,000
High 60,000 80,000 80,000 100,000 120,000
* Airflow shown is for bottom only return ---air supply with factory ---supplied 1 ---in. washable filter(s). For air delivery a bove 1800 CFM, see Air D el ivery table for
other options.
{ Low heat CFM when low---heat rise adjustment switch (SW1 ---3) on furnace control is used.
} AFUE and capacity in accordance with U.S. Government DOE test procedures.
** Gas input ratings are certified for elevations to 2000 ft. For elevations above 2000 ft, redu ce ratings 2% for each 1000 ft above sea level. In Ca nada, derate
the unit 5% for el eva tions from 2000 to 4500 ft above sea level.
58UVB