NO. Item Specification outline Remarks
2 Outdoor fan
control
1. All cooling fan control
1) Outdoor fan speed (mode) is controlled on the basis of measurements provided
by the Pd pressure sensor.
2) For a specified period after the start of cooling operation, the header outdoor
unit controls outdoor fan speed (mode) on the basis of measurements provided
by the Pd pressure sensor. Follower units, on the other hand, control outdoor fan
speed (mode) on the basis of measurements provided by the TE1 temperature
sensor.
• The fan speed
corresponding to
the highest mode
varies with the
Ton capacity of
the outdoor unit.
283 (1.95)
290 (2.00)
312 (2.15)
341 (2.35)
355 (2.45)
384 (2.65)
435 (3.0)
[Highest mode]
[Current mode + 1]
(Mode raised as rapidly 
as every second)
[Current mode + 1]/50 seconds
[Hold]
[Current mode + 1]/75 seconds
(Mode raised up to 13)
(Mode 1 to highest)
[Current mode - 1]/50 seconds
Mode being lowered:
Highest mode - 1   1
Mode being raised: mode 0   1
[Current mode - 1]
(Mode lowered as rapidly as 
every two seconds)
(down to mode 0)
Interval control
[Mode [0]: 180 seconds
Mode [1]: 30 seconds]
Pd
pressure
psi (MPa)
* Available control modes are 0 (at rest) to 63.
2. All heating fan control
1) Outdoor fan speed (mode) is controlled on the basis of measurements provided
by the TE1 temperature sensor.
2) If TE1 > 77°F (25°C) is continuously detected for 8 minutes, the fan may be
turned off.
However, this condition is the same as normal thermo OFF, so that fan operation
will be restarted.
3) For a specified period after air conditioner startup and during defrosting, this
control is disabled.
4) When refrigerant is in extremely short supply, this control may cause the air
conditioner to be repeatedly turned on and off.
77 (25)
46.4 (8)
42.8 (6)
39.2 (4)
35.6 (2)
Zone A: Lowest mode, timer count for forced compressor shutdown
Zone B: -2/30 seconds (down to lowest mode)
Zone C: -1/30 seconds (down to lowest mode)
Zone D: Hold (staying at current mode)
Zone E: +1/30 seconds (up to highest mode)
Zone F: Highest mode
TE1 temperature
˚F (˚C)
3. Mainly cooling fan control
The outdoor fan rps (mode) is controlled by the objective condensation
temperature (Pd) during mainly cooling operation.
• The fan speed
corresponding to
the highest mode
varies with the Ton
capacity of the
outdoor unit.
[Mode at present + 1] / Until Min.1 second
[Mode at present + 1] / 40 seconds
HOLD (Keeps the mode at present)
[Mode at present – 1] / 40 seconds
[Mode at present – 1] / 16 seconds
[Mode at present – 1] / 2 seconds
466 (3.21)
Pd (psi(MPa))
455 (3.14)
426 (2.94)
415 (2.86)
400 (2.76)
450 (3.10)
At heating
thermo-ON
At heating
thermo-OFF
426 (2.94)
395 (2.72)
387 (2.67)
373 (2.57)
4. Control while follower unit stops
To prevent refrigerant stagnation into heat exchanger of the outdoor unit, operate
the fan with Mode 1. (Except defrost operation)
• The fan speed
corresponding to
the highest mode
varies with Ton
capacity of the
outdoor unit
• This control may
cause the air
conditioner to be
fan stop.