(5) Individual start/stop (ON/OFF) individual test operation function
This function is provided to start/stop (ON/OFF) individually each indoor unit connected to the same system by
using switches on the interface P.C. board of the header unit.
Set SW01 [16] and set SW02, SW03 to indoor address No. (1 to 40) to be started (Refer to the following
table*) - only the setup indoor unit starts operation.
(In the rotary switches of the indoor unit which operates in a group by the remote controller, the follower unit
cannot be individually started or stopped. In this case, [ - - ] is displayed on 7-segment display [B] on the
interface P.C. board of the header unit.)
<Operation procedure>
NOTE) The individual test operation returns to the normal operation after 60 minutes.
*
SW01 SW02 SW03
Units to be operated
16 1
16 2
16 3
Address 1 to 
Address 16 } 
individually
Address 17 to 
Address 32 } 
individually
Address 33 to 
Address 40 } 
individually
In individual 
start/stop
1~16
1~16
1~16
Power ON
Start
End
(7-segment display)
[A]
[         ]
[B]
[         ]
(7-segment display)
[A]
[         ]
[B]
[         ]
(7-segment display)
[A]
[         ]
[B]
[         ]
Be sure to turn on power at the indoor side 
before power-ON of outdoor unit.
Set up the operation mode of the remote controller.
(If it is not set up, the operation continues with the 
current mode.)
Push the push switch SW04 on the same board for 2 
seconds or more.
(If pushed continuously for 10 seconds or more, the 
operation changes to the individual test operation.)
Match the rotary 
switches on the 
interface P.C. 
board of the 
header unit to the 
following table*.
If an error is already displayed with SW01/SW02/SW03 
being [1/1/1], return the status to normal one according 
to troubleshooting and then execute a test operation.
The unit which is not given with priority by heating 
priority control, cooling priority control, and selection 
of cooling or heating mode is not operated.
In this case, "     operation ready" or "      operation 
mode controlled" is displayed on the remote controller.
Address display 
of corresponding 
indoor unit
Address display 
of corresponding 
indoor unit
[ 11] is displayed for 5 seconds after operation-ON.
(For individual test operation, [ FF] is displayed.)
[ 00] is displayed 
for 5 seconds after 
operation-ON.
Address display 
of corresponding 
indoor unit
[ 00] is displayed 
for 5 seconds after 
operation-ON.
Operation check
If the discharge temperature does not change 
though COOL or HEAT has been set up from the 
remote controller, misconnection is considered.
The indoor unit to be started operates.
Push the push switch SW05 
on the interface P.C. board of 
the header unit for 2 seconds 
or more.
After test operation, return the display select switches 
SW01/SW02/SW03 on the interface P.C. board of the 
header unit to [1/1/1].
SW04 SW05
SW02 SW03SW01
7-segment display [A] 7-segment display [B]
<Rotary switches>