[F08]
[F10]
[F12]
[F07]
[F13]
Sub-code: 01: Compressor 1, 02: Compressor 2, 03: Compressor 3
TL sensor error
TL sensor Open/Short
TO sensor error
TO sensor Open/Short
Indoor TA sensor error
TA sensor Open/Short
TS1 sensor error
TS1 sensor Open/Short
TH sensor error
IGBT built-in sensor error in A3-IPDU
This error code means IGBT built-in temperature sensor error.
Check connection of connectors CN06 on IPDU P.C. board and CN600 on I/F P.C. board.
If sensor is normal, replace IPDU P.C. board.
This error code means detection of Open/Short of TL sensor. Check disconnection of circuit for connection of
connector (TL sensor: CN523, White) and characteristics of sensor resistance value. (See "Outdoor unit temperature
sensor characteristics" on "9-9. Sensor Characteristics".)
If sensor is normal, replace outdoor I/F P.C. board.
This error code means detection of Open/Short of TO sensor. Check disconnection of circuit for connection of
connector (TO sensor: CN507, Yellow) and characteristics of sensor resistance value. (See "Outdoor unit temperature
sensor characteristics" on "9-9. Sensor Characteristics".)
If sensor is normal, replace outdoor I/F P.C. board.
This error code means detection of Open/Short of TA sensor. Check disconnection of circuit for connection of
connector (TA sensor: CN104, Yellow) and characteristics of sensor resistance value. (See "Indoor unit temperature
sensor characteristics" on "9-9. Sensor Characteristics".)
If sensor is normal, replace indoor P.C. board.
This error code means detection of Open/Short of TS1 sensor. Check disconnection of circuit for connection of
connector (TS1 sensor: CN505, White) and characteristics of sensor resistance value. (See "Outdoor unit temperature
sensor characteristics" on "9-9. Sensor Characteristics".)
If sensor is normal, replace outdoor I/F P.C. board.
Open/short of TF / TFA sensor was detected. Check disconnection of connector connection (TFA sensor: CN103
yellowish green) circuit and resistance value characteristics of the sensor. (Refer to "9-9 Sensor Characteristics
Indoor Unit Temperature Sensor Characteristics".) When the sensor is normal, replace the indoor P.C. board.
Yes
Outdoor I/F P.C. board
TE1 sensor : CN520, Green
TL sensor : CN523, White
No
No
Yes
No
Yes
[F15]
Outdoor temp sensor miswiring
(TE1 , TL)
1. Misinstallation and misconnection of TE1 sensor
and TL sensor
2. Resistance characteristics error of TE1 sensor
and TL sensor
3. Outdoor P.C. board (I/F) error
Are
installed positions
of TE1 sensor and TL
sensor correct?
Are
connection
of TE1 sensor connector
and TL sensor connector
normal?
Are
resistance
characteristics of TL
sensor and TE1 sensor
normal?
Correct installed positions of
TE1 sensor and TL sensor.
Correct connection of
connectors.
Correct connection of
connectors.
Check outdoor I/F P.C. board.
Defect → Replace
TE1 sensor : Outdoor heat exchanger temp sensor
TL sensor: Temp sensor between liquid tanks of outdoor PMV1/2
* See "Outdoor unit temperature sensor characteristics" on "9-9. Sensor Characteristics".
Check code
Cause
Check code name
Check code
Cause
Check code name
Check code
Cause
Check code name
Check code
Cause
Check code name
Check code
Cause
Check code name
Check code
Cause
Check code name