– 192 –
Switching of Jumper Wire/Function Setup
*4 When you replace the board with a service board, be sure to cut the jumper wire matching with the outdoor
unit model to be installed. (The jumper wires J09 to J12 which were mounted at shipment from the factory
are provided to all the boards regardless of model type.)
O
: With jumper,
×
: Without jumper (Cut)
Function switching setup
jumper Part type Exchange contents
Initial setting
at shipment
J01
O
O
Optional function
Operation mode selection
operation switching
Indoor unit at not selected side is kept with waiting status.
J16
O
O
Demand control 1 (Standard
specification)
Corresponds to 2-core wire
Normal (3-core wire <Successive MAKE signal> or
4-core wire <Successive MAKE or Pulse signal>)
×
2-core wire <Successive MAKE signal>
J09
J12Setup for service
P.C. board
(Model setup)
O
Approx. 75% (Normal)
×
The mode is changed a mode which selected the operation mode of the
indoor unit at not selected side.
O
J12
O
At shipment from factory *4
O
MAP0724FT
×
MAP0964FT
×
J11
O
O
×
×
J10
O
×
×
×
J09
O
O
×
O
MAP1204FT
J11
O
O
×
Approx. 60%
J04
O
Upper limit setup of demand
capacity command in
corresponding indoor during
saving operation in indoor
O
J10