7
Installation
FEATURE
PARAMETER
NUMBER
DESCRIPTION
VALUE
RANGE
DEFAULT
VALUE
INSTALLER
VALUE
Min Max
ALARM OR
DEFROST
SELECTION
108
This parameter will select the output on
J7 Pin4.
12 2
1. With this conguration J7PIN4 is HIGH if there
are activated any Unit alarms &/or Defrost
2. With this conguration J7PIN4 is HIGH if there
are activated any Unit alarms
FROST DELTA SP 109
This parameter is dening the delta set point
versus MIN COOL WT to activate the frost
threshold limit °C (KGEL)
06 0
RESET COMP RUN
TIME
110
This parameter is to give reset the compressor
time to zero
000 165 000
FLOW SWITCH
STATUS
111
This parameter will display the Flow Switch
status:
01
Read
status
1. Water Flowing
0. Water not owing
HEAT CLIMATIC
NUMBER
112
Selection of Heat Climatic Curve Number:
06 0
0. No predened Climatic Curve
(Installer has to draw Climatic Curve)
1 - 6. See Climatic curve details
HEAT WSP 113
Fixed Heating Water Set Point in case of the
System is not used with the Comfort NUI
20°C 60°C 45°C
ECO HEAT T° RED 114
Temperature reduction value for xed HEAT
Water Set Point (ECO)
1°C 20°C 5°C
COOL WSP 115
Fixed Cooling Water Set Point in case of the
system is not used with the Comfort NUI control
4°C 25°C 7°C
ECO COOL T° RED 116
Temperature reduction value for xed COOL
Water Set Point (ECO)
1°C 10°C 5°C
COOL CLIMATIC
NUMBER
117
Selection of Cool Climatic Curve number:
02 0
0. No predened Climatic Curve
(Installer has to draw Climatic Curve)
1 - 2. See Climatic curve details
REGION T° O
HEATING
118
Minimum outdoor Temperature depending on
the country where the system is installed
-20°C 10°C -7°C
STOP H T° O
HEATING
119
The system stop to heat when the outdoor
Temperature is equal or greater than the value of
this parameter
10°C 30°C 20°C
NO HEAT T W1
HEATING
120
In heating mode, minimum water Temperature
going to terminal zone 1
20°C 60°C 40°C
MAX W T° W1
HEATING
121
In heating mode, maximum water Temperature
in terminal zone 1
20°C 60°C 55°C
MAX REGION
COOLING
122
Max region outside Temperature depending on
the Country where the system is installed
24°C 46°C 40°C
COOL STOP T°
COOLING
123
The system stop to Cool when the outdoor
Temperature is equal or superior to the value of
this parameter
0°C 30°C 22°C
MIN COOL W T°
COOLING
124 In Cool mode, minimum water Temperature 4°C 20°C 4°C
MAX COOL W
COOLING
125 In Cool mode, max water Temperature 4°C 20°C 12°C
OAT INSTALLED 126
1. GMC OAT sensor installed
12 2
2. GMC OAT sensor not installed
CDU T°O 127
Outdoor Temperature value measured
by the CDU sensor
-- -
REFRIG TC 128 Coil refrigerant value measured by the CDU - - -
SUCTION T° 129 Compressor Suction Temperature - - -
DISCHARGE T° 130 Compressor Discharge Temperature - - -