Installation
DEFROST / TFC
SELECTION
147
This parameter will select the output on Terminal
Block
12 1
1. 5/N signal on H version shall be 230V or 9/19
signal on X version shall be dry contact closed in
case of defrost
2. With this conguration, 5/N signal on H
version shall be 230V or 9/19 signal on X version
shall be dry contact closed if room temperature
reach the air temperature set point
EXT HEAT OAT LIMIT 148 Outdoor Temperature Limit -20 65 -10
TEMP LIST 149
NUI shall display these temperatures in
temperature zone.
17 1
1. Room T
2. LWT
3. EWT
4. Refrigerant
5. Suction
6. Discharge
7. TE
The parameters which are read only and are not editable by user, Key pad lock ( ) icon will be displayed on the screen for
those parameters.
At installation ll in the installer value if default value has been changed.
FEATURE
PARAMETER
NUMBER
DESCRIPTION
VALUE
RANGE
DEFAULT
VALUE
INSTALLER
VALUE
Min Max