17
Table 2 — Electrical Data
LEGEND
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or HACR circuit breaker.
Canadian units may be fuse or circuit breaker.
2. Wire sizing amps are a sum of 125% of the compressor RLA plus
100% of indoor fan motor FLA.
3. Motors are protected against prim
ary single phasing condition.
4. Indoor-fan motors are 3-phase motors of same voltage as unit.
Table 3 — Fan Electrical Data
LEGEND
NOTE: The FLA data listed in this table is for one fan only. When
calculating system FLA, evaporator fan and condenser fan must be
included.
UNIT
50XCA
V-PH-Hz
VOLTAGE
RANGE
COMPRESSOR
NO. 1
COMPRESSOR
NO. 2
Min Max RLA LRA RLA LRA
06
208/230-3-60 187 253 18.3 136
460-3-60 414 506 8.8 66
575-3-60 518 632 6.6 55
08
208/230-3-60 187 253 23.0 149
460-3-60 414 506 11.0 75
575-3-60 518 632 8.0 54
12
208/230-3-60 187 253 15.6 110 15.9 110
460-3-60 414 506 7.8 52 7.1 52
575-3-60 518 632 5.8 39 5.1 39
14
208/230-3-60 187 253 19.6 136 19.2 136
460-3-60 414 506 8.2 66 8.7 66
575-3-60 518 632 6.6 55 6.9 55
16
208/230-3-60 187 253 28.7 191 23.0 149
460-3-60 414 506 13.3 100 11.0 75
575-3-60 518 632 10.0 78 8.0 54
24
208/230-3-60 187 253 40.7 240 28.7 191
460-3-60 414 506 19.3 140 13.3 100
575-3-60 518 632
15.6 107 10.0 78
LRA Locked Rotor Amps
NEC National Electrical Code
RLA Rated Load Amps
MOTOR
CODE
MOTOR
HP
V-PH-Hz
VOLTAGE
RANGE
FLA
Min Max
B 0.50
208/230-3-60 187 253 1.8/2.2
460-3-60 414 506 1.1
575-3-60 518 632 0.9
C 0.75
208/230-3-60 187 253 2.5/2.6
460-3-60 414 506 1.3
575-3-60 518 632 1.0
D 1.00
208/230-3-60 187 253 3.2/3.2
460-3-60 414 506 1.6
575-3-60 518 632 1.1
E 1.50
208/230-3-60 187 253 4.6/4.8
460-3-60 414 506 2.4
575-3-60 518 632 1.6
F 2.00
208/230-3-60 187 253 6.0/5.8
460-3-60 414 506 2.9
575-3-60 518 632 2.1
FLA Full Load Amps

Related product manuals