EasyManua.ls Logo

Carrier Omnizone 50XCA06 - Page 24

Carrier Omnizone 50XCA06
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
Table 7 — Condenser Fan Performance — 50XCA14 Units
LEGEND
Bhp — Brake Horsepower
ESP External Static Pressure
NOTES:
1. Units are available with several motor hp options. Refer to Table 1.
2. Static pressure losses for any options or accessories must be
applied to external static pressure before entering the fan perfor-
mance table.
3. Interpolation is permitted; extrapolation is not.
4. Fan performance is based on unit casing, and wet DX (direct
expansion) c
oil losses at sea level.
CFM
ESP (in. wg)
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
6000 496 1.03 533 1.17 570 1.36 608 1.58 646 1.82 683 2.06 719 2.31 755 2.56
6250 517 1.17 552 1.31 588 1.50 624 1.72 660 1.97 696 2.22 732 2.48 766 2.74
6500 537 1.31 571 1.46 605 1.65 640 1.88 675 2.13 710 2.39 744 2.66 778 2.93
6750 558 1.47 590 1.62 623 1.81 657 2.05 691 2.30 724 2.57 757 2.85
7000 579 1.64 610 1.79 642 1.99 674 2.23 707 2.49 739 2.76
7250 599 1.82 629 1.98 660 2.18 691 2.42 723 2.68 754 2.96
7500 620 2.02 649 2.18 679 2.38 709 2.62 739 2.89
7750 641 2.23 669 2.39 697 2.59 726 2.84
8000 661 2.45 688 2.61 716 2.82
8250 682 2.69 708 2.85
8500 703 2.94
8750
9000
9250
9500
CFM
ESP (in. wg)
0.80 0.90 1.00 1.10 1.20
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
6000 789 2.81
6250 800 3.00
6500
6750
7000
7250
7500
7750
8000
8250
8500
8750
9000
9250
9500

Related product manuals