24
Table 7 — Condenser Fan Performance — 50XCA14 Units
LEGEND
Bhp — Brake Horsepower
ESP — External Static Pressure
NOTES:
1. Units are available with several motor hp options. Refer to Table 1.
2. Static pressure losses for any options or accessories must be
applied to external static pressure before entering the fan perfor-
mance table.
3. Interpolation is permitted; extrapolation is not.
4. Fan performance is based on unit casing, and wet DX (direct
expansion) c
oil losses at sea level.
CFM
ESP (in. wg)
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
6000 496 1.03 533 1.17 570 1.36 608 1.58 646 1.82 683 2.06 719 2.31 755 2.56
6250 517 1.17 552 1.31 588 1.50 624 1.72 660 1.97 696 2.22 732 2.48 766 2.74
6500 537 1.31 571 1.46 605 1.65 640 1.88 675 2.13 710 2.39 744 2.66 778 2.93
6750 558 1.47 590 1.62 623 1.81 657 2.05 691 2.30 724 2.57 757 2.85 — —
7000 579 1.64 610 1.79 642 1.99 674 2.23 707 2.49 739 2.76 — — — —
7250 599 1.82 629 1.98 660 2.18 691 2.42 723 2.68 754 2.96 — — — —
7500 620 2.02 649 2.18 679 2.38 709 2.62 739 2.89 — — — — — —
7750 641 2.23 669 2.39 697 2.59 726 2.84 — — — — — — — —
8000 661 2.45 688 2.61 716 2.82 — — — — — — — — — —
8250 682 2.69 708 2.85 — — — — — — — — — — — —
8500 703 2.94 — — — — — — — — — — — — — —
8750 — — — — — — — — — — — — — — — —
9000 — — — — — — — — — — — — — — — —
9250 — — — — — — — — — — — — — — — —
9500 — — — — — — — — — — — — — — — —
CFM
ESP (in. wg)
0.80 0.90 1.00 1.10 1.20
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
6000 789 2.81 — — — — — — — —
6250 800 3.00 — — — — — — — —
6500 — — — — — — — — — —
6750 — — — — — — — — — —
7000 — — — — — — — — — —
7250 — — — — — — — — — —
7500 — — — — — — — — — —
7750 — — — — — — — — — —
8000 — — — — — — — — — —
8250 — — — — — — — — — —
8500 — — — — — — — — — —
8750 — — — — — — — — — —
9000 — — — — — — — — — —
9250 — — — — — — — — — —
9500 — — — — — — — — — —