PA4S, PA5S: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
Notes:
- Optimum performance point, 95°F (35°C) outdoor ambient and (80°F / 27°C dry bulb), (67°F / 19°C wet bulb) indoor conditions. (DOE A Test Conditions)
- Where a dash (—) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in.
- Superheat °F is at low-side service port, Allow a tolerance of ±3°F (±1.7°C)
- Indoor dry bulb between 70°F and 80°F (21°C and 27°C)
Table 2 – Rating Plate (required) Subcooling Temperatures
Measure
 Liquid Pressure 
(psig)
R-410A Required Liquid Line Temperature °F (°C)
°F (°C) °F (°C) °F (°C) °F (°C) °F (°C) °F (°C)
6 3 8 4 10 6 12 7 14 8 16 9
251  78  26  76  24  74  23  72  22  70  21  68  20 
259  80  27  78  26  76  24  74  23  72  22  70  21 
266  82  28  80  27  78  26  76  24  74  23  72  22 
274  84  29  82  28  80  27  78  26  76  24  74  23 
283  86  30  84  29  82  28  80  27  78  26  76  24 
291  88  31  86  30  84  29  82  28  80  27  78  26 
299  90  32  88  31  86  30  84  29  82  28  80  27 
308  92  33  90  32  88  31  86  30  84  29  82  28 
317  94  34  92  33  90  32  88  31  86  30  84  29 
326  96  36  94  34  92  33  90  32  88  31  86  30 
335  98  37  96  36  94  34  92  33  90  32  88  31 
345  100 38  98  37  96  36  94  34  92  33  90  32 
364  104 40  102  39  100  38  98  37  96  36  94  34 
374  106 41  104  40  102  39  100  38  98  37  96  36 
384  108 42  106  41  104  40  102  39  100  38  98  37 
395  110 43  108  42  106  41  104  40  102  39  100  38 
406  112 44  110  43  108  42  106  41  104  40  102  39 
416  114 46  112  44  110  43  108  42  106  41  104  40 
427  116 47  114  46  112  44  110  43  108  42  106  41 
439  118 48  116  47  114  46  112  44  110  43  108  42 
450  120 49  118  48  116  47  114  46  112  44  110  43 
462  122 50  120  49  118  48  116  47  114  46  112  44 
474  124 51  122  50  120  49  118  48  116  47  114  46 
Table 3 – Superheat Charging - AC Only
OUTDOOR TEMP (°F) 
EVAPORATOR ENTERING AIR TEMPERATURE (°F WB) 
50  52  54  56  58  60  62  64  67  68  70  72  74  76 
55  9  12  14  17  20  23  26  29  32  35  37  40  42  45 
60  7  10  12  15  18  21  24  27  30  33  35  38  40  43 
65  —  6  10  13  16  19  21  24  27  30  33  36  38  41 
70  —  — 
7  10  13  16  19  21  24  27  30  33  36  39 
75  —  —  —  6  9  12  15  18  21  24  28  31  34  37 
80  —  —  —  —  5  8  12  15  18  21  25  28  31  35 
85  —  —  —  —  —  —  8  11  15  19  22  26  30  33 
90  —  —  —  —  —  —  5  9  13  16  20  24  27  31 
95  —  —  —  —  —  —  —  6  10  14  18  22  25  29 
100  —  —  —  —  —  —  —  —  8  12  15  20  23  27 
105  —  —  —  —  —  —  —  —  5  9  13  17  22  26 
110  —  —  —  —  —  —  —  —  —  6  11  15  20  25 
115  —  —  —  —  —  —  —  —  —  —  8  14  18  23 
Table 4 – Required Suction-Line Temperature
SUPERHEAT TEMP (°F) 
SUCTION PRESSURE AT SERVICE PORT (PSIG) 
107.8  112.2  116.8  121.2  126  130.8  138.8  140.8  145.8 
0  35  37  39  41  43  45  47  49  51 
2  37  39  41  43  45  47  49  51  53 
4  39  41  43  45  47  49  51  53  55 
6  41  43  45  47  49  51  53  55  57 
8  43  45  47  49  51  53  55  57  59 
10  45  47  49  51  53  55  57  59  61 
12  47  49  51  53  55  57  59  61  63 
14  49  51  53  55  57  59  61  63  65 
16  51  53  55  57  59  61  63  65  67 
18  53  55  57  59  61  63  65  67  69 
20  55  57  59  61  63  65  67  69  71 
22  57  59  61  63  65  67  69  71  73 
24  59  61  63  65  67  69  71  73  75 
26  61  63  65  67  69  71  73  75  77 
28  63  65  67  69  71  73  75  77  79 
30  65  67  69  71  73  75  77  79  81 
32  67  69  71  73  75  77  79  81  83 
34  69  71  73  75  77  79  81  83  85 
36  71  73  75  77  79  81  83  85  87 
38  73  75  77  79  81  83  85  87  89 
40  75  77  79  81  83  85  87  89  91