There should not be any heat source or stream 
near the unit.
There should not be any obstacles blocking the 
air circulation.
A place where air circulation in the room is good.
A palce where drainage can be easily done.
A palce where noise prevention is taken into 
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the 
wall,ceiling,fence or other obstacles.
There should not be any direct sunlight. If unavoidable, 
sunlight prevention should be taken into consideration.
1. Fit the installation plate horizontally
    on structural parts of the wall with 
    spaces around the installation plate.
2. If the wall is made of brick, concrete 
    or the like, drill eight (8) 5mm diameter 
    holes in the wall.Insert Clip anchor for 
    appropriate mounting screws.
3. Fit the installation plate on the wall 
    with eight (8) type    A     screws.
Fit the Installation Plate and drill 
holes in the wall according to the 
wall structure and corresponding 
mounting points on the installation 
plate. The installation plate 
provided with the machine differ 
from appliance to appliance. 
(Dimensions are in   mm   unless 
  otherwise stated)
Correct orientation 
of Installation Plate
1. Determine hole positions according  to left and right 
    side of the installation plate. The hole center is obtained 
    by measuring the distance as shown in the diagram above. 
2. Dirll the piping plate hole with φ65mm hole-core drill.
3. Drill the piping hole at either the right or the left and the 
    hole should be slightly slanted to the outdoor side.
4. Always use wall hole conduit when drilling metal grid, 
    metal plate or the like.
1. For the left-hand and right-hand  piping, 
    remove the pipe cover from the side panel.    
2. For the rear-right-hand and rear-left-hand 
    piping, install the piping as shown. 
3. Bundle the tubing, connecting cable, and 
    drain hose with tape securely,  evenly as 
    shown in Figure on the right.
       Because the condensed water from rear 
       of the indoor unit is gathered in ponding  
       box and is piped out of room. Do not put 
       anything else in the box.
1. Run the drain hose sloping downward. 
    Do not install the drain hose as illustrated 
    in Figures.
2. When connecting extension drain hose, 
    insulate the connecting part of extension  
    drain hose with a shield pipe, do not let 
    the drain hose slack.
Connect the indoor unit first, then the 
outdoor unit. 
Do not allow the piping to let out from the 
back of the indoor unit.
Be careful not to let the drain hose slack.
Heat insulated both of the auxiliary piping. 
Be sure that the drain hose is located at 
the lowest side of the bundle. Locating at 
the upper side can cause drain pan to 
overflow inside the unit.
Never intercross nor intertwist the power 
wire with any other wiring.
Run the drain hose slopped downward to 
drain out the condensed water smoothly.
Anchor the outdoor unit with a bolt and nut  φ10 or 
φ8 tightly and horizontally on a concrete or rigid mount.
O
ut
d
oor 
u
ni
t 
d
ime
n
s
i
o
n
 m
m
(L1
x
H
x
W1)
L2(mm) W2(mm)
530
290
560
549
481
335
276
276
Mounting dimensions
760x590x285
845x700x320
780x540x250
670x540x265
1. Pass the piping through the hole in the wall.
2. Hook the indoor unit onto the upper portion 
    of installation plate(Engage the indoor unit with 
    the upper edge of the installation plate). Ensure 
    the hooks are properly seated on the installation 
    plate by moving it in left and left.
3. Piping can easily be made  by lifting the indoor 
    unit with a cushioning material between the 
    indoor unit and the wall. Get it out after finish 
    piping.
4. Press the lower left and right side of the unit 
    against the installation plate until hooks 
    engages with the their slots.
INSTALLATION MANUAL FOR ROOM
AIR CONDITIONER
(Split Wall-Mounted Type)
SELECT THE BEST LOCATION
Indoor  unit
DRILL A HOLE IN THE WALL 
Outdoor  unit
Settlement of  outdoor unit
FIT THE INSTALLATION PLATE
2 
CONNECTIVE PIPE AND DRAINAGE INSTALLATION 
3 
NOTE:
NOTE:
Fit the Installation Plate
Connective pipe installation
Draina ge
CAUTION
Indoor unit installation
1
 
The mounting wall is strong and solid
enough to prevent it from the vibration. 
" " 
" 
" 
If an awning is built over the unit to prevent 
direct sunsight or rain,be careful that heat 
radiation from the condenser is not obstructed.
There should not be any animal or plant which 
could be affected by hot air discharged.
Keep the spaces indicated by arrow from wall 
ceiling, fence or other obstacles.
Do not place any obstacles which may cause 
a short circuit of the discharged air.
I
N
D
O
O
R 
U
N
I
T 
150mm or more to ceiling
Indoor unit outline
Installation plate
292
Right rear side 
refrigerant
pipe hole φ65
Left rear side 
refrigerant
pipe hole φ65
120mm or 
more to wall
120mm or 
more to wall
920
45
185
150
45
A
45
B
Right rear side 
refrigerant
pipe hole φ65
Installation plate
Indoor unit outline
Left rear side 
refrigerant
pipe hole φ65
150mm or more to ceiling
120mm or 
more to wall
120mm or 
more to wall
 Model A (A: 710, B: 250, C:100, D: 160)
Model B(  )A: 790, B:265, C:100, D: 150 
Model C
Model D
45
C
D
 The seriousness is classified by the following indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property.
1)  This equipment must be earthed and installed with earth leakage current breaker. It may cause 
electrical shock if grounding is not perfect.
             
2)  Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and 
 accumulates at surrounding of the unit, it may cause fire.
3)  Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water 
 may enter the room and damage the furniture.
1)  Install according to this installation instructions strictly. If installation is defective, it will cause water
leakage, electrical shock fire.
       
2) Use the attached accessories parts and specified parts for installation, otherwise, it will cause the set 
to fall, water leakage, electrical shock fire.
             
3)  Install at a strong and firm location which is able to withstand the set s weight. If the strength is not 
enough or installation is not properly done, the set will drop and cause injury.
                           
4)  For electrical work, follow the local national wiring standard, regulation and this installation instructions. 
An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or
                                   
defect found in electrical work, it will cause electrical shock fire.
                     
5)  Use the specified cable and connect tightly and clamp the cable so that no external force will be acted 
on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
                                     
6)  Wiring routing must be properly arranged so that control board cover is fixed properly. If control board
cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
                                   
7)  When carrying out piping connection, take care not to let air substances other than the specified 
refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure
                             
in the refrigeration cycle, explosion and injury.
             
8)  Do not modify the length of the power supply cord or use of extension cord, and do not share the 
single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
                           
SAFETY PRECAUTIONS
CAUTION
WARNING
CAUTION
WARNING
      Please read this installation manual completely before installing the product.
      If the power cord is damaged, replacement work shall be performed by authorised personnel only.
      Installation work must be performed in accordance with the national wiring Standards by authorised 
      personnel only. 
      Contact an authorised service technician for repair, maintenance or installation of this unit.
      This appliance is not intended for use by persons(including children) with reduced physical, sensory
     or mental capabilities, or lack of experience and knowledge, unless they have been given supervision
     or instruction concerning use of the appliance by a person responsible for their safety. 
     Children should be supervised to ensure that they do not play with the appliance.
 
The design and specifications are subject to change without prior notice for product improvement. 
     Consult with the sales agency or manufacturer for details.
 
All the pictures in the instructions are for explanation purposes only. The actual shape should prevail.
 
 
1
2
3
4
5
7
8
9
6
Installation Plate
Clip Anchor
Self-tapping Screw A ST3.9x25 
Seal(For cooling & heating models only)
Drain Joint(For cooling & heating models only) 
Connec ti ng 
pipe 
Assemb ly
Liquid s id e 
Gas side
Remote controller 
Self-tapping Screw B ST2.9x10 
Φ6.35
Φ9.52
Φ9.52
Φ12.7
Φ 16 
Parts you must purchase. The pipe 
size differ from appliance to appliance. 
Consult the technician for the proper 
size.
1
5-8(de pe nd ing on models )
5-8(de pe nd ing on models )
1
1
1
2
1
Except the above parts provided,the other parts needed during installation you must 
purchase.
Remote controller holder
ACCESSORIES
Number
Name of  Accessories
Qty 
NOTE:
option al 
parts
120mm or more
  from  the wall
120mm or more  
from the wall
45
150mm or more from the ceiling
Indoor Unit Outline
70
Hooked Part
110
1080
330
65
65
4
5
    2020001B3679
STELLAR INVERTER SERIES