66
To convert BHP to watts, use 84% motor efficiency. To convert BHP to watts, use 84% motor efficiency.
Table F — 48LC**06 Direct Drive (Horizontal)
SPEED
(TORQUE) TAP
CFM ESP BHP
1
1250 0.04 0.18
1500
1750
1875
2000
2125
2250
2375
2500
2
1250 0.99 0.63
1500 0.55 0.58
1750 0.14 0.53
1875 0.01 0.49
2000
2125
2250
2375
2500
3
1250 1.24 0.76
1500 0.88 0.77
1750 0.44 0.73
1875 0.24 0.70
2000 0.07 0.66
2125
2250
2375
2500
4
1250 1.33 0.81
1500 1.07 0.89
1750 0.74 0.93
1875 0.56 0.88
2000 0.36 0.91
2125 0.15 0.88
2250
2375
2500
5
1250 1.35 0.82
1500 1.12 0.92
1750 0.86 1.00
1875 0.72 1.04
2000 0.56 1.08
2125 0.39 0.95
2250 0.19 1.09
2375
2500
Table G — 48LC**06 Direct Drive (Vertical)
SPEED
(TORQUE) TAP
CFM ESP BHP
1
1250 0.03 0.16
1500
1750
1875
2000
2125
2250
2375
2500
2
1250 0.89 0.57
1500 0.41 0.53
1750 0.03 0.49
1875
2000
2125
2250
2375
2500
3
1250 1.15 0.72
1500 0.74 0.72
1750 0.30 0.68
1875 0.10 0.65
2000
2125
2250
2375
2500
4
1250 1.20 0.76
1500 0.94 0.83
1750 0.59 0.87
1875 0.40 0.82
2000 0.20 0.83
2125 0.01 0.80
2250
2375
2500
5
1250 1.28 0.78
1500 1.00 0.87
1750 0.71 0.95
1875 0.57 0.98
2000 0.41 1.01
2125 0.25 0.88
2250 0.06 1.01
2375
2500