b. Press (Down arrow key) once. The following dis-
play appears:
c. Press OK. The following display appears:
d. Press (Down arrow key) once to move the high-
light to the bottom row, then press OK. The following
display appears:
e. Press ▼ (Down arrow key) again. The following dis-
play appears:
f. Press (Down arrow key) again. The following dis-
play appears:
g. Press (Down arrow key) again. The following dis-
play appears:
NOTE: By pressing OK the number in the bracket can be changed
until the desired number appears. Press OK again to set the select-
ed value.
11. Set Analog Inputs:
a. Press the Back key until the following display
appears:
b. Press (Down arrow key) until the following dis-
play appears:
c. Press OK. The following display appears:
d. Press (Down arrow key) once to move the high-
light to the bottom row, then press OK. The following
display appears:
e. Press (Down arrow key) once to move the high-
light to the bottom row, then press OK. The following
display appears:
f. Press (Down arrow key) once to move the high-
light to the bottom row, then press OK. The following
display appears:
g. Press (Down arrow key) once to move the high-
light to the bottom row, then press OK. The following
display appears:
12. Set Reset Mode and RFI Filter:
a. Press the Back key until the following display
appears:
b. Press (Down arrow key) until the following dis-
play appears:
c. Press OK. The following display appears:
d. Press ▼ (Down arrow key) twice. The following dis-
play appears:
e. Press OK. The following display appears:
f. Press OK to highlight the number in the bracket.
g. Use the (Up arrow) and (Down arrow) keys to
change the number to 3 for 2 automatic resets; then
press OK. The display changes to:
h. Press (Down arrow key) once. The following dis-
play appears:
i. Press OK to highlight the number of seconds and use the
(Up arrow) and (Down arrow) keys to select
600 seconds. Press OK again to set the selected value.
j. Press the Back key once. The following display
appears:
k. Press ▼ (Down arrow key) twice. The following dis-
play appears:
l. Press OK. The following display appears:
m. Press OK to highlight the number in the brackets and use
the ▲ (Up arrow) and ▼ (Down arrow) keys to select
0. Press OK again to set the selected value.
13. Complete reprogramming: Press the Auto On key before
disconnecting the VFD Remote Keypad from the variable
frequency drive.
4—** Limits/Warnings
5—** Digital In/Out
5 —0* Digital I/O Mode
5 —1* Digital Inputs
5 —10 Terminal 18 Digital In...
[8] Start
5 —11 Terminal 19 Digital In...
[16] Preset ref bit 0
5 —12 Terminal 27 Digital In...
[17] Preset ref bit 1
5 —12 Terminal 29 Digital In...
[18] Preset ref bit 2
4—** Limits/Warnings
5—** Digital In/Out
5—** Digital In/Out
6—** Analog In/Out
6—**Analog In/Out
6—1* Analog Input 53
6 —10 Terminal 53 Low Voltage
2V
6 —11 Terminal 53 High Voltage
[10V]
6 —14 Set Min Reference
[0 Hz]
6 —15 Set Max Reference
[60 Hz]
0 —** Operation/Display
1 —** Load and Motor
13—** Smart Logic
14—** Special Functions
14 —0* Inverter Switching
14 —1* Mains On/Off
14—1* Mains On/Off
14—2* Reset Functions
14 —20 Reset Mode
[0] Manual reset
14 —20 Reset Mode
[3] Automatic reset x 3
24 —21 Automatic Restart T...
10s
14—1* Mains On/Off
14—2* Reset Functions
14—4* Energy Optimizing
14—5* Environment
14 —50 RFI Filter
[1] On

Table of Contents