EasyManua.ls Logo

Carrier WeatherMaker 48TC Series - Protective Devices; Compressor Protection; Supply (Indoor) Fan Motor Protection

Carrier WeatherMaker 48TC Series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31
low voltage wire and the high voltage circuit. Route the low volt-
age wire to the central terminal board. See Fig. 40.
NOTE: If utilizing the through the base connections, route the low
voltage wire through the wire ties to the central terminal board.
Fig. 40 — Typical Low-Voltage Control Connections
Heat Anticipator Settings
Set heat anticipator settings at 0.14 amp for the first stage and
0.14 amp for second-stage heating.
Transformer Connection for 208-v Power Supply
All units except 208/230-v units are factory wired for the voltage
shown on the nameplate. If the 208/230-v unit is to be connected
to a 208-v power supply, the control transformer must be rewired
by moving the black wire with the
1
/
4
-in. female spade connector
from the 230-v connection and moving it to the 208-v
1
/
4
-in. male
terminal on the primary side of the transformer. Refer to unit label
diagram for additional information.
Humidi-MiZer
®
Control Connections
HUMIDI-MIZER – SPACE RH CONTROLLER
NOTE: The Humidi-MiZer system is a factory installed option
which is available for size 17, 20, 24 and 28 units equipped with
RTPF condenser coils.
The Humidi-MiZer dehumidification system requires a field-sup-
plied and installed space relative humidity control device. This de-
vice may be a separate humidistat control (contact closes on rise in
space RH above control setpoint) (see Fig. 42) or a combination
thermostat-humidistat control device such as Carriers EDGE
®
Pro Thermidistat (see Fig. 43) with isolated contact set for dehu-
midification control. The humidistat is normally used in applica-
tions where a temperature control is already provided (units with
PremierLink™ control).
To Connect the Carrier Humidistat (HL38MG029):
1. Route the humidistat 2-conductor cable (field-supplied)
through the hole provided in the unit corner post.
2. Feed wires through the raceway built into the corner post (see
Fig. 41) to the 24-v barrier located on the left side of the con-
trol box. The raceway provides the UL-required clearance
between high-voltage and low-voltage wiring.
3. Use wire nuts to connect humidistat cable to two PINK leads
in the low–voltage wiring as shown in Fig. 44.
To connect the Thermidistat device (33CS2PPRH- 01)
1. Route the Thermidistat multi-conductor thermostat cable
(field-supplied) through the hole provided in the unit corner
post.
2. Feed wires through the raceway built into the corner post (see
Fig. 42) to the 24-v barrier located on the left side of the con-
trol box. The raceway provides the UL-required clearance
between high-voltage and low-voltage wiring.
3. The Thermidistat has dry contacts at terminals D1 and D2
for dehumidification operation (see Fig. 45). The dry con-
tacts must be wired between CTB terminal R and the PINK
lead to the LTLO switch with field-supplied wire nuts.
Refer to the installation instructions included with the Car-
rier Edge Thermidistat device for more information.
Fig. 41 — Field Control Wiring Raceway
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may cause a short circuit.
Carefully check the connection of control conductor for indoor
fan control at terminal G. Connecting the indoor fan lead to ter-
minal C will cause a short circuit condition, which can cause
component damage inside the unit or at the thermostat.
C
W2
G
W1
R
Y1
TYPICAL
THERMOSTAT
CORRECTIONS
O/B/Y2
(SEE NOTE)
NOTE: Typical multi-function marking. Follow manufacturer’s configuration
instructions to select Y2.
Field Wiring
CENTRAL
TERMINAL
BOARD
W1
Y2
Y1
R
W2
G
C
X
W1
Y2
Y1
R
W2
G
C
X
T–STAT
SEE
CAUTION
RUBBER
GROMMET
CORNER
POST
WIRE
TIES
THRU THE BASE
CONNECTION

Table of Contents

Other manuals for Carrier WeatherMaker 48TC Series

Related product manuals