25
Fig. 45 — Edge Pro Thermidistat
Connecting the Carrier Humidistat (HL38MG029)
1. Route the humidistat 2-conductor cable (field-supplied)
through the hole provided in the unit corner post.
2. Feed wires through the raceway built into the corner post (see
Fig. 43) to the 24-v barrier located on the left side of the con-
trol box. The raceway provides the UL-required clearance
between high-voltage and low-voltage wiring.
3. Use wire nuts to connect humidistat cable to two PINK leads
in the low-voltage wiring as shown in Fig. 46.
Connecting the Thermidistat device (33CS2PPRH-01)
1. Route the Thermidistat multi-conductor thermostat cable
(field-supplied) through the hole provided in the unit corner
post.
2. Feed wires through the raceway built into the corner post (see
Fig. 43) to the 24-v barrier located on the left side of the con-
trol box. The raceway provides the UL-required clearance
between high-voltage and low-voltage wiring.
3. The Thermidistat has dry contacts at terminals D1 and D2 for
dehumidification operation (see Fig. 47). The dry contacts
must be wired between CTB terminal R and the PINK lead to
the LTLO switch with field-supplied wire nuts. Refer to the
installation instructions included with the Carrier Edge Pro
Thermidistat device for more information.
Fig. 46 — Typical Humidi-MiZer Adaptive Dehumidification System Humidistat Wiring