7.7. To change other datas
IMPORTANT
If, when settings are adjusted, no key is activated within 5 sec. the system reverts to displaying
the box temperature. All changes made are recorded.
1. Press the SET key (6.) during 5 seconds to enable access to malfunction codes (see 7.9. for alarm
list).
2. Press the -- or + key (5. or 7.) to display alarms
3. Press the SET key (6.) to display software versions.
4. Press the + key (7.) to display cab command software version.
5. Press the SET key (6.) to display road hourmeter.
6. Press the SET key (6.) to display standby hourmeter .
7. Press the DEFROST key (4.) to display the defrost interval (mn) calculated by the microprocessor
between 2 defrosts.
8. Press the DEFROST key (4.) again to display elapsed time (mn) since the last defrost.
9. Press the SET key (6.) to return to box temperature display .
7.8. To change default parameters
IMPORTANT
If, when settings are adjusted, no key is activated within 5 sec. the system reverts to displaying
the box temperature. All changes made are recorded. Malfunction codes remain displayed.
1. Press simultaneously the -- and + and DEFROST keys (5. and 7. and 4.) to display minimum setpoint.
2. Press the -- or + key (5. or 7.) to change the minimum setpoint : 0_C, - 20_Cor-29_C (default value
-- 2 9 _C)
3. Press the SET key (6.) to display maximum setpoint.
4. Press the -- or + key (5. or 7.) to change the maximum setpoint : + 20_Cor+30_C (default value
+20_C)
5. Press the SET key (6.) to display differential parameter .
6. Press the -- or + key (5. or 7.) to adjust the differential value : Dif1 (1_C), Dif2 (2_C) or Dif3 (3_C)
(default value Dif2).
7. Press the SET key (6.) to display evaporator fan operating mode during of f--cycle.
8. Press the -- or + key (5. or 7.) to change the evaporator fan operating mode : FOFF or F On (FOFF by
default).
9. Press the SET key (6.) to return to box temperature display .