Installing Heat Reclaim Ventilation
Power Connection Denition
1. Wiring Notice—Shut o󰀨 Power Prior to Whatever Job.
The machine must be connected to the ground according EN 60364.
Circuit breaker capable of shutting power o󰀨 the whole system shall be installed. Please make sure that earth
connection is available.
A switch and fuse shall be available for every single power line. Circuit or creepage breaker shall be available
for whatever wiring job.
Make sure that ground impedance does not exceed 100 ohms. When creepage breaker is available, ground
impeder can be used to accommodate impedance over 500 ohms.
Power line, connection line, air switch shall be prepared by users.
Power line model: YZW power line; size must meet local criteria. Must adopt the triple-core shielded wire
with sleeve, such as H05VV-F, H05RN-F, H07RN-F, which are approved by local authority. The size of
the conductor shall not less than 0.75mm2. While connecting the power line, make sure current-carrying
conductors become taut before earthing conductor, if the cord slips out of the cord anchorage.
Fuse Spec: 15A.
Power lines of di󰀨erent specs shall not be connected to the same terminal. Overheating will ensue in case of
loose terminal connection.
Power lines of di󰀨erent specs shall not be connected to the same ground terminal. Protection will be impaired
in case of loose connection.
Keep certain distance between power lines and other connection cables to prevent noise.
For wiring method, refer to circuit diagram. Wiring notice: every cable shall be connected to its corresponding
terminal according to its unique polarity, and shall have its sign matched up with terminal sign.
2. Open and Close Electrical Cabinet
Before opening the cabinet cover, make sure that power connections to unit components are shut o󰀨.
Unscrew bolts xing the cover and open the cabinet.
Fix power line with clamp and make sure that earth connection is available. Connect control and signal lines
to corresponding terminal blocks.
Please use shield wire as signal line.
Upon completing wiring job, please mount the cabinet cover in good manner.
25