Remote Configuration – INSTALLER LEVEL
Infrared remote configuration
To enter the remote configuration mode in the remote, the DOWN ARROW button must be
depressed with the LOUVER button for 5 continuous seconds while the remote is in Off
mode.
The remote will clear its display. The configuration item will be displayed in the two digit
temperature display and the value of that item will be displayed in the four-digit time display.
The configuration initially displays whatever the previously saved value was, if there is no
previous value, the items will display the default value. The remote will initially display the
configuration item “CH” for remote configuration. In order to store the infrared remote’s
value, press the LOUVER button
.
+
+
Press the louver
button to store
the value
Configuration Item Value Description
“CH Ab : Both
A : Channel A
b : Channel B
Remote ID selection
Defaults to Ab
“tU C : Degrees C
F : Degrees F
Temperature units
Defaults to C
“rc HP : Normal Operation
CO : Cooling Only
Puts the Remote into Cooling
Mode only
Defaults to HP
“HR 17 – 32 : 17° -32° C
63 – 90 : 63° -90° F
Maximum heating setpoint.
Degrees C or F is determined by
“tU” configuration above.
“CR 17 – 32 : 17° -32° C
63 – 90 : 63° -90° F
Minimum cooling setpoint.
Degrees C or F is determined by
“tU” configuration above.
“CL 12 : 12 Hour Standard (AM/PM)
24 : 24 Hour Military
Time Format
Defaults to 12
Infrared OFF mode
At least for 5
continuos seconds
First item shown