FORCECLIMA 12600 SOUNDLESS HEATING FORCECLIMA 12600 SOUNDLESS HEATING
7372
ENGLISH ENGLISH
2. Purge the circuit with inert gas.
3. Evacuate.
4. Purge again with inert gas.
5. Open the circuit by cutting or brazing.
- The refrigerant charge must be recovered from the correct recovery cylinders. The system
to be repeated several times. Oxygen or compressed air must not be used for the task.
- Cleanliness must be achieved by breaking the vacuum in the system with oxygen-
is no refrigerant left in the system. When using the oxygen-free nitrogen end-charge,
the system must be vented to atmospheric pressure to allow for work. This operation is
absolutely vital if brazing operations are to take place on pipes.
- Ensure that the vacuum pump outlet is not near any source of ignition and that ventilation
is available.
8. Loading procedure
-
refrigerant contained in them.
- Cylinders must be kept in an upright position.
- Ensure that the refrigeration system is grounded before loading the system with
refrigerant.
-
-
Before reloading, the system must be pressure-tested with oxygen-free nitrogen. The system
leakage test must be carried out before leaving the site.
9. Commissioning
Before performing this procedure, it is essential that the technician is thoroughly familiar with
safely recovered. Before the task is carried out, a sample of oil and refrigerant should be taken
be power before starting with the task.
A.
B. Electrically isolate the system.
C. Before attempting the procedure, ensure that:
-
3. Repair of intrinsically safe components
- Do not apply any permanent inductive or capacitive load to the circuit without ensuring
- Intrinsically safe components are the only type of components that can be worked on
features.
-
the refrigerant in the atmosphere from a leak.
4. Wiring
Verify that the wiring is not subject to wear, corrosion, excessive pressure, vibration, sharp
5. Detection of ammable refrigerants
Under no circumstances should potential ignition sources be used in the search for or detection
6. Leak-detection methods
- The following leak-detection methods are considered acceptable for systems containing
-
be calibrated in a refrigerant-free area). Ensure that the detector is not a potential ignition
-
containing chlorine must be avoided, as chlorine can react with the refrigerant and corrode
copper pipes.
-
-
the leak. Oxygen-free nitrogen must then be purged through the system both before and
during the brazing process.
7. Removal and evacuation
When intervening in the cooling circuit for repairs or any other purpose, conventional
procedures must be followed. However, it is important that best practices are followed, as
1. Remove the refrigerant.