- 39 -
Speed governing
electronic
Capacity of oil sump
9 l
Capacity of cooling system
9 l
Electrical system
12 Vdc
Emission compliance
iT4
Power circuit
Circuit-breaker, 3-ph.
Number of poles
4
Thermal release It (thermal release is higher at 25°C)
32 A
Magnetic release Im
3..5xIn
Circuit-breaker, 3-ph., lower voltage
Number of poles (optional)
NA
Thermal release It (thermal release is higher at 25°C)
NA
Magnetic release Im
NA
Unit
Dimensions (LxWxH) 2097.1 x 950 x 1141 mm
Weight net mass
709 kg
Weight wet mass
824 kg
Notes
1) Reference conditions for engine performance to ISO 3046-1.
2) See derating diagram or consult the factory for other conditions.
3) At reference conditions unless otherwise stated.
4) Rating definition (ISO 8528-1):
LTP: Limited Time Power is the maximum electrical power which a generating set is capable of delivering (at variable load), in the event of a utility power failure (for up
to 500 hours per year of which a maximum of 300 hours is continuous running). No overload is permitted on these ratings. The alternator is peak continuous rated (as
defined in ISO 8528-3) at 25°C.
PRP: Prime Power is the maximum power available during a variable power sequence, which may be run for an unlimited number of hours per year, between stated main-
tenance intervals and under the stated ambient conditions. A 10% overload is permitted for 1 hour in 12 hours. The permissible average power output during a 24h period
shall not exceed the stated load factor of 80%.
5) Specific mass fuel used: 0.86 kg/l.
Technical specifications for CPG 25 Kubota