- 24 -
Replace safety cartridge x
Check alternator and starter motor x
Check electrical system for security of cables and wear x
Test thermostats x
Test glow plugs x
Inspection by Chicago Pneumatic Service technician
Generators in standby application have to be tested on a
regular basis. At least once a month the engine should run for
minimum 30 minutes at a high load (50% - 70%) that the
engine reaches its operating temperature.
Notes:
In highly dusty environments, these service intervals do not apply. Check and/or replace filters and clean radiator on a regular basis.
(1) During engine break-in, change the oil and oil filter for the first time after max. 50 hours of operation.
(2) Air filter should be replaced sooner when the unit is operating in a dusty environment.
(3) Adjust/replace coolant as necessary.