Technical specifications for CPG 25 Kubota
Readings on gauges
Settings of switches
Specifications of the engine/alternator/unit
Gauge Reading Unit
Ammeter L3 (P3) Below max. rating A
Voltmeter (P4) Below max. rating V
Switch Function Activates at
Engine oil pressure Shut down 0.5 bar
Engine coolant temperature Shut down 105°C
60 Hz
Reference conditions 1)
Rated frequency 60 Hz
Rated speed (optional)
1800 rpm
Generator service duty
PRP
Absolute air inlet pressure
100 kPa
Relative air humidity
30%
Air inlet temperature
25°C
Limitations 2)
Maximum ambient temperature 50°C
Altitude capability
4000 m
Maximum relative air humidity
85%
Minimum starting temperature unaided -2
°C
Minimum starting temperature aided (optional)
-25°C
Performance data 2) 3) 5)
Rated active power (PRP) 3ph 18.6 kW
Rated active power (PRP) 1ph (optional)
17.3 kW
Rated power factor (lagging) 3ph
0.8 cos
Rated power factor (lagging) 1ph (optional)
1.0 cos
Rated PRP power 3ph
23.3 kVA
Rated PRP power 1ph (optional)
17.3 kVA
Rated voltage 3ph. line to line
480 V
Rated voltage 3ph. line to line lower voltage
240 V
Rated voltage 1ph (optional)
240 V
Rated current 3ph.
28.6 A
Rated current 3ph. lower voltage
56.1 A
Rated current 1ph. (optional)
72.1 A
Performance class (acc.ISO 8528-5:1993) (optional)
G2
Single step load acceptance (0-PRP)
18.6 kW
100%