P- Parameters
P00 Power-down recovery function 0:off;1:on 1
P01 Single / three phase selection 0:Single-phase power supply Three-phase power
supply
0
P02 Power frequency 5:50HZ; 6:60HZ 6
P03 Heat source selection 0:Geo; 1:Air source 1
P04 Heating temperature control method 0:Method 1 : 1:Method 2 0
P05 Defrost method selection 0:Method 1 : 1:Method 2 0
P06 FREECOOLING validation 0:valid; 1:invalid 1
P07 Frequency control method 0:Method 1; 1:Method 2 0
P08 DHW validation 0:valid; 1:invalid 0
P09 Air conditioning and heating validation 0:valid; 1:invalid 0
P10 Air conditioning and Cooling validation 0:valid; 1:invalid 0
P11 DHW hot water temp hysteresis 2~15℃,minus hysteresis 2℃
P12 AC temp hysteresis 2~15℃,minus hysteresis 2℃
P27 Max percentage speed of compressor 55~100% 100%
P30 fan motor Category 0:AC Fan;1:EC Fan1 2:EC Fan2 1
P31 Maximum speed of the fan 1-10(10=100%)
100
P32 Heating fan speed control temperature difference 2~15℃ 4
P33 Cooling Fan speed control Temperature difference 5~18℃ 6
P34 Defrost method 0:Method 1; 1:Method 2 0
P35 defrost starting temp -5~5℃ -1℃
P36 defrost interval time multiple rate 0:Not defrost;1;2;3;4:(intervalX4) 1
P37 The first defrost interval 15~99minute(1st interval after repower on) 35
P38 defrost exist temp 10~35℃ 30℃
P39 Start Defrost air-coil difference 0-40℃ 8