P-Parameters
P40 Electric heater start delay minute 5-15min 10
P41
SSR Ramp Up rate 1-20min 5
P42
Automatic heating temperature 0-17 0
P43
Automatic cooling temperature 0-28 0
P45
Allowed defrost coil temperature -20~5 -6
P47
hot water frequency limitation 2~10= max frequency 20~100% 10
P48
AC heating AU mode highest temp 30~50 45
P49
AC Heating AU mode offset temperature -10~10 0
P50
solenoid valve function parameters 0G3 is seasonal valve1G3is solar
valve
0
P51
C4 Water pump type selection 0AC Water pump 1EC Water
pump
1
P52
water pump working mode 0(Not stop) 1.stop after reach target
temp2start 1 minute after each
stop 15 minutes
0
P53
EC Water pump C4 Minimum speed 20-80% 4
P54
C5 Water pump type selection 0AC Water pump 1:EC water pump 0
P55
DHW e-heater activated ambient temp -20~20 0
P56
Electric heating function 0 Electric heater1 second heat
source
0
P57
AC e-heater activated ambient temp -20~20 0
P58
2nd heat source starting air temp -30~15 -15
P59
AC anti-freezing temperature -15~5 3
P60
Virus killing interval days 7~99 day 7day
P61
Start virus killing time 1~24 hour 1
P62
Virus killing holding time 5~360 Min 10
P63
Target temperature of virus killing 55~80 65