NVF5 Series User Manual Appendix A RS485-MODBUS
Communication Instructions
Description Address Explanation
Power
Down
Saving
Read-write
property
Communication
CommandF0.01 =
2Communication
Command
0x3200
0x00No command
No W
0x01Forward running
0x02Reverse running
0x03Run stop
0x04Forward jog
0x05Reverse jog
0x06Jog stop
0x07Free stop
0x08Fault reset
Status 0x3300
bit00Run / Stop (0 Stop,
1 Run)
/
R
bit01Reverse / Forward
(0 forward, 1 reverse)
bit02Zero-speed
operation(1 effective)
bit03Accel (1 effective)
bit04Decel(1 effective)
bit05Operation at
constant
speed (1 effective)
bit06Pre-Flux
(1 effective)
bit07
Tuning (1
effective)
bit08Overcurrent
limited
(1 effective)
0x09DC overvoltage
limited
(1 effective)
bit10Torque limited
(1 effective)
bit11
Speed limited (1
effective)
- 106 -