- 8 -
Items Specification Standards
Ambient Temp.
-10℃–65℃
-
-25℃–80℃
-
Ambient
5–95% RH, Not Condensed
-
5–95% RH, Not Condensed
-
Vibration
For Discontinuous Vibration
IEC 61131-2
Frequency Acceleration Amplitude
Times
5 ≤ f < 9 Hz - 3.5 mm
X,
10 times
9 ≤ f ≤ 150 Hz
9.8 m/s
(1G) -
Continuous Vibration
Frequency Acceleration Amplitude
Times
5 ≤ f < 9 Hz - 1.75 mm
X,
10 times
9 ≤ f ≤ 150 Hz
4.9 m/s
(0.5G) -
Shock
Max. impact acceleration: 147 m/s
2
(15G)
Authorized time: 11 ms
Pulse wave: Sign half-wave pulse (3 times each in X, Y, Z)
IEC 61131-2
Noise
Square Wave
±2 kV
CIMON
Standard
Electrostatic
Voltage: ±4 kV (contact), ±8 kV (air)
IEC 61131-2
IEC 61000-4-2
Radiated
E
80–1000 MHz, 10 V/m
IEC 61131-2
IEC 61000-4-3
Fast Transient
Burst Noise
Unit
Power
Module
Digital I/O
(24 V or
more)
Digital I/O
(less than 24V)
Analog I/O
Comm. interface
IEC61131-2
IEC61000-4-4
Voltage
2 kV 2 kV 1 kV
Ambient
No corrosive gas or dust
2,000 m or less
Pollution Degree 2 or less
Natural air cooling
General Specifications