EasyManuals Logo

Circutor CVM-NRG96 Manual

Circutor CVM-NRG96
2 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
CVM-NRG96-ITF-BACnet-C
M98238701-03-15A
3.- CVM-NRG96 communication
The unit incorporates BACNet MS/TP communication, following the specifications of
ANSI/ASHRAE 135 (ISO 16484-5). Using a RS485 connection, the analyzer can
connect to a BACnet and include all of the objects and services defined in the
attached PICS map (Protocol Implementation Conformance Statement). Instant,
maximum and NRG96mum variables can be read.
The default speed is 38400 bps and the MAC is 2 (node number), and can be
changed with the keyboard or by writing the BaudRate and MAC_Address variables.
The identifier (Device_ID) can be changed with the keyboard, with write property or
by writing the Device_ID variable. Another option is to write on the Object_Name in
Device:
a) #Baud x where x may be: 9600, 19200, 38400, 57600, 76800, 115200 bps
b) #MAC x where x may be: 1 ... 127
c) #ID x where x may be: 1 ... 4194303
For further information on the protocol www.bacnet.org
.
4.- TECHNICAL FEATURES
Power circuit:
- Single-phase :
- Voltage tolerance :
- Frequency :
- Maximum consumption :
- Working temperature :
- Humidity (no condensation)
- Altitude :
230 V a.c.
-15...10 %
50 - 60 Hz
1,8 ... 3,6 VA
-10 ..+ 50 ºC
5 .. 95%
2000 m
Metering circuit:
- Nominal voltage: phase-neutral / phase-phase
- Frequency :
- Minimum current
- Nominal current :
- Permanent overload :
- Voltage Input consumption:
- Current Input consumption: ITF / Shunt
300 V a.c. / 520 V a.c.
45 ~ 65 Hz
50mA
I
n
/5A or /1A
1.1 In
0.7 VA
0.9 VA / 0.75 VA
Mechanical features:
- Case material :
- Protection : Fitted unit (frontal) :
Non-fitted unit (sides and rear cover) :
- Dimensions (mm) :
- Weight:
Self extinguishing V0 plastic
IP 51
IP 31
96 x 96 x 63
400 g
Features of the output transistors
- Type: Opto-isolated transistor
- Maximum switching voltage :
- Maximum switching current :
- Maximum frequency :
- Impulse duration :
(open collector)NPN
24 V d.c.
50 mA
5 pulses / second
100 ms
Accuracy class:
- Voltage :
- Current :
- Powers :
Measurement conditions :
- Voltage :
- Current :
- Power Factor :
- Scale range measurement margin: ITF / Shunt
0.5 % ± 2 digits
0.5 % ± 2 digits
1 % ± 2 digits
Direct or indirect measurement with transformer
Indirect measurement by means of transformer
0.5 to 1
0,2...120% / 2...120%
Safety:
Installation category III / EN61010. Double-insulated electric shock protection class II. The
equipment must be connected to a power circuit protected with type gl fuses, in compliance
with IEC 269, or type M, with values from 0.5 to 1A. It must be fitted with a circuit breaker
switch or an equivalent device, in order to be able to disconnect the equipment from the power
supply grid. The NRG96mum diameter of the power supply cable shall be 1mm
2
.
Standards:
IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-6-3,
EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 55011
5.- CONNECTIONS
4 wires / 3 wires ( low voltage )
3 wires (2 voltage and 3 current transformers)
3 wires (2 voltage and 2 current transformers)
6.- TECHNICAL SERVICE
If you have any doubts about the operation of the unit or suspect any malfunction, contact our service staff at CIRCUTOR, SA
CIRCUTOR, SA - Technical Assistance Service
Vial Sant Jordi, s/n
08232 Viladecavalls (Barcelona), SPAIN
Tel: 902 449 459 (España)
Tel: (+34) 93 745 29 00 (outside Spain)
email: sat@circutor.es
Power Supply V a.c. / c.c.
Power Supply V a.c. / c.c.
Power Supply V a.c. / c.c.

Other manuals for Circutor CVM-NRG96

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Circutor CVM-NRG96 and is the answer not in the manual?

Circutor CVM-NRG96 Specifications

General IconGeneral
BrandCircutor
ModelCVM-NRG96
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals