Code
Type Sensivity (A) Tripping delay (s)
Communications
P24622
RGU - 10 RAL
0,03-0,1-0,3-0,5-1-3
by direct adjustment
 
5-10-30 by SETUP
INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1
              by direct adjustment
3-5-10 by SETUP
No Available
P 2 X X X X 0 0 X
Código
 Code
Código interno
 Internal code
Tensión de
alimentación
Power supply
230 V a.c. 
110 V a.c.
0
1
RGU-10 RAL Electronic earth leakage protection relay with self-reclosing system
For instance, RGU-10 RAL supplied by 110 V a.c. 
GENERAL DESCRIPTION
-  Device with programmable differential relay with self-reclosing system. Symbol          in LCD.
-  It has 2 independents outputs by relays. Trip and locked by reclosing.
-  It has 1 input for  external Trip/Reclose. This input is opto - coupled.
-  Mounting in Rail DIN  46277 (EN 50022) or panel 72x72 by mean accessory (M5ZZF1)
-  Associated to a WG/WGS Series external , toroidal current transformer.
-  It must be asociated to CONTACTOR like breaking element.
-  It verifies connection with differential transformer WG/WGS by means inductive test.
-  Leakage detection and measurement is via calculating its true efective value (TRMS).
-  Display settings values and instant residual current to its accociated units.
 
DESCRIPTION LED AND BUTTONS.
-  Shows equipment status via a display and 2 LED.
-  5 button  equipment setup and setting.
-  2 button  equipment TEST and RESET.
INDICATION BY LED AND DISPLAY.
-  TRIP RELAY. LED and display signals a change 
   of status by changing from green to red.l 
   Display event type messages or values.
-  BETWEN RECLOSURES. 
 The yellow LED is blinking. Red Display shows the
   tripp cause fluctuating with partial reclosures No
-  LOCKED BY RECLOSURES.      
   The yellow LED is  fixed. The equipment arrives al
   maximun number of reclosures established by the
   self-reclosing sequence. Red display shows the cause.
-  No OF RECLOSURES. By short press on PROG the display shows the number of reclosures by
   earth leakage faults, partial and total number. The partial number are floating pages. In these 
   pages it can configure the self-reclosing sequence by press REC button.  
RECLOSING THE EQUIPMENT.
-  BY TRIP / LOCKED BY RECLOSURES
   1.  Automathic (earth leakage fault or manual). Is Shown on display
   2.  Manual reclose by pushing button RESET
   3.  External reclose sytem by remote or communications signal. When it forces a trip by  remote 
   signal, only it can reclose by another remote signal.
In the case 2 and 3 the all partial counters of reclosures returns to a zero.
 
RELAY PARAMETERS SETTING ( t , I  y std/+ )
d d
-  , t . 
d
SETTING TRIP DELAY The               message   and two   values   appear  on the  screen  after 
  pressing  the button.  The lowest  value indicates   the current   set value  and the highest  is the  t
d    
  values to be configured which are  displayed by pressing The  selected  value to be  saved  is       .  
  displayed by showing the message SAVE.
-  , I .  I . . 
d d
SENSITIVITY SETTING The same operation as above setting is carried out by pressing 
- SIGNALLING CONTACTS RELAY STATE,  std/+ . Select the default position of the relay contacts 
  4-5-6 that indicates the situation of locked by reclosures of the device .  In (Std) 4-6 NO  / 4-5 NC 
  and (+) 4-5 NC  / 4-6 NO and  appears the     symbol in display.
- SELF-RECLOSING SYSTEM, REC.   In   reclosure   partial   numbers   by press  REC  button we 
  configure the self-reclosing  sequence  referred  at  the  page which it’s showing us.  By default  is 
  configured  nº1 by  earth leakage protection.
PROG
+
Others MESSAGES by display
SAVE
EXIT
OVR
ERRt
Enter setting values 
Exits setting mode
Value reading off scale
Poor toroidal conection
M98204601-03-20A
P24262001
  PARAMETERS BY 
DIRECT ADJUSTMENT 
-DELAY SETTING
-SETUP ROTATION
-SENSIVITY SETTING 
-CONTACTS SETTING NO/NC
-ENABLE/DISABLE 
 SELF-RECLOSING SYSTEM 
REC
RECLOSE SEQUENCES BY EARTH LEAKAGE CURRENT FAULT 
- Varistor Features
  Maximun Voltage:  275 Va.c.
-Characteristics input remote Trip/Reclose 1-2
  Input using optocoupler
Max. Voltage: 230 Va.c.; 0,7 W
TECHNICAL FEATURES
- Tipo Relay type: Electronic class A. High frequency current filtering.
- Reclosing type: Authomatic, RESET button or by cutting power supply.
- Rated power supply voltage: 230 o 110 Va.c. (+/- 20%)  50/60 Hz, 6 VA
 
-  :  -10ºC / 50ºCOperating temperature
-  :Connections
2
  0,127 - 2,082 mmPermissible cable section:          
  Recommended tightening torque: 0.5-0.6 Nm
  Length of cable to strip:                 7 mm
 
-   13-14-15 and 4-5-6.Switch Output contact features
  : 6/10 A a.c.Rated current/Maximum instant current
  : 250/230 V a.c.Rated voltage/Maximum switching voltage
   AC: 2,500 V·ARated load in
  Contacts protected by varistor
REC
REC
RAL
 Maximun DC Load Breaking
 Capacity:
 Maximun opening current
Electrical useful life for 
AC 
loads: No of cycles
¡ IMPORTANT !
The relay only self-recloses after a trip by earth leakage current fault. The Test (red button) only verifies the relay trips 
the protection. It recloses only by manual pressing RESET button.
REC
REC
  (LOCKED SIGNAL)
(See graph)
(See graph)
Tripping cause
Message display
Test
Remote signal trip/reclose
Earth leakage fault
TESt
EXT
DIF / value
- GREEN LED: ON 
- RED LED: TRIPPED BY FAULT
- YELLOW LED: Locked by reclosures (fix)/ Betwen reclosures (blinking)
- RESET Button
- Test Button
- SCREENS / SETUP 
R
     With the button  the submenus are browsed PROG
                            and with the        button the  values to  be selected 
                            are displayed. 
                            Press    PROG to  enter  the value. The  equipment 
                            configures the  value by  displaying on  “SAVE” por 
                            the display and then exits Setting Mode.
 If  the   keypad remains  inactive for a certain time, 
                            the   equipment   automatically exits  Setting Mode 
                            and displays without changing the setting “EXIT”  .
                           - SP t configures the status contact relay, NO/NC:
                                                          13- 15 / 6 - 4
                           - RSTC reinitiates the partial counter. 
Button
FREQ
LIM
SEC.T
Button
   60 Hz
10 s, 30 A
RST.C
   SI
Button PROG
   SI
   50 Hz
1 s,   3 A
   NO
   NO
- FREQ, ( ) frecuency (Hz)50
- LIM,( ), range of values (Id / td)1s, 3A
- SEC. T,  ( ),contacts  status relayNO
 14-15-16 [NA/NC] trip relay
 4-  5-   6[NA/NC] pre-alarma
- RST.C, ( ), NO
 Initiates the partials counters.
Default values in SETUP
SETUP SETTINGS
PROG
SREC    No RECLOSURES                TIME SEQUENCES                             RESET TIME
   0                                                                     DISABLED
   1                      6                                 8, 16, 30, 59, 115 and 224 s                   15 minutes
   2                    30                                 20, 40 s and 5 min. to the end                15 minutes
   3                      8                                 30 s, 1, 2, 3, 4, 5, 6 and 7 min                15 minutes
   4                      6                                 10, 20, 30, 60, 130 and 600 s                 15 minutes
   5                      6                                 2, 4 y 8 min. to the end                           15 minutes
   6                      7                                 30 s, 1, 2, 3, 4, 8 and 16 min                  30 minutes
   7                    10                                 1 min                                                       30 minutes
   8                    10                                 90 s                                                         30 minutes
   9                      8                                 2, 4 y 6 minutes to the rest                     15 minutes
 10                    10                                 3 minutes                                                30 minutes
 11                      7                                 2, 4, 8, 16, 32, 32 and 32 minutes          15 minutes
 12                    31                                2, 4 and 6 minutes to the rest                  15 minutes
 13                      6                                8 s                                                            15 minutes
 14                     ...                                  ...                                                             ...