RGU-10 MT Electronic earth leakage protection relay with self-reclosing system
GENERAL DESCRIPTION
- Device with programmable differential relay with self-reclosing system. Symbol in LCD.
- It has 2 independents outputs by relays. Trip and locked by reclosing.
- It has 1 input for external Trip/Reclose. This input is not opto - coupled.
- Mounting in Rail DIN 46277 (EN 50022) or panel 72x72 by mean accessory (M5ZZF1)
- Associated to a WG/WGS Series external , toroidal current transformer.
- It must be asociated to a MCB motorized with or without a trip coil.
- It verifies connection with differential transformer WG/WGS by means inductive test.
- Leakage detection and measurement is via calculating its true efective value (TRMS).
- Display settings values and instant residual current to its accociated units.
DESCRIPTION LED AND BUTTONS.
- Shows equipment status via a display and 2 LED.
- 5 button equipment setup and setting.
- 2 button equipment TEST and RESET.
INDICATION BY LED AND DISPLAY.
- TRIP RELAY. LED and display signals a change
of status by changing from green to red.l
Display event type messages or values.
- BETWEN RECLOSURES.
The yellow LED is blinking. Red Display shows the
tripp cause fluctuating with partial reclosures No
- LOCKED BY RECLOSURES.
The yellow LED is fixed. The equipment arrives al
maximun number of reclosures established by the
self-reclosing sequence. Red display shows the cause.
- No OF RECLOSURES. By short press on PROG the display shows the number of reclosures by
earth leakage, short ciruit-overload faults and total number. The partial number are floating pages
In these pages it can configure the self-reclosing sequence by press REC button.
RECLOSING THE EQUIPMENT.
- BY TRIP / LOCKED BY RECLOSURES
1. Automathic (earth leakage, short ciruit-overload faults or manual). Enabled.
2. Manual reclose by pushing button RESET
3. External reclose sytem by remote or communications signal. When it forces a trip by remote
signal, only it can reclose by another remote signal.
4. Manual reclose circuit breaker associated.
In the case 2 and 3 the all partial counters of reclosures returns to a zero.
RELAY PARAMETERS SETTING ( t , I y std/+ )
d d
- , t .
d
t
d
.
SAVE.
- , I . I . .
d d
- SIGNALLING CONTACTS RELAY STATE, std/+ . Select the default position of the relay contacts
7-8-9 that indicates the situation of locked by reclosures of the device . In (Std) 8-7 NA / 8-9 NC
and (+) 8-7 NC / 8-9 NA and appears the symbol in display.
- SELF-RECLOSING SYSTEM, REC. In reclosure partial numbers by press REC button we
configure the self-reclosing sequence referred at the page which it’s showing us. By default is
configured nº10 by earth leakage protection and nº5 by short-circuit/overload protection.
SETTING TRIP DELAY The message and two values appear on the screen after
pressing the button. The lowest value indicates the current set value and the highest is the
values to be configured which are displayed by pressing The selected value to be saved is
displayed by showing the message
SENSITIVITY SETTING The same operation as above setting is carried out by pressing
Tripping cause
Message display
Test
Remote signal trip/reclose
Earth leakage fault
Short circuit / Overload fault
TESt
EXT
DIF / valor
MAG
PROG
+
Others MESSAGES by display
SAVE
EXIT
OVR
ERRt
Enter setting values
Exits setting mode
Value reading off scale
Poor toroidal conection
PARAMETERS BY
DIRECT ADJUSTMENT
-DELAY SETTING
-SETUP ROTATION
-SENSIVITY SETTING
-CONTACTS SETTING NO/NC
-ENABLE/DISABLE
SELF-RECLOSING SYSTEM
REC
SREC No RECLOSURES TIME SEQUENCES RESET TIME
RECLOSE SEQUENCES BY EARTH LEAKAGE CURRENT FAULT
SREC No RECLOSURES TIME SEQUENCE RESET TIME
RECLOSE SEQUENCE BY SHORTCIRCUIT/OVERLOAD FAULT
TECHNICAL FEATURES
Relay type: Electronic class A. High frequency current filtering.
- Reclosing type: Authomatic, RESET button or by cutting power supply.
- Rated power supply voltage
Operating temperature
Connections
Permissible cable section:
Recommended tightening torque: 0.5-0.6 Nm
Length of cable to strip: 7 mm
Switch Output contact features
Rated current/Maximum instant current
Rated voltage/Maximum switching voltage
Rated load in
- Tipo
:
- : -10ºC / 50ºC
- :
2
0,127 - 2,082 mm
- 13-14-15, 7-8-9 and 5-6
: 6/10 A a.c.
: 250/230 V a.c.
AC: 2,500 V·A
Contacts protected by varistor
- Varistor Features
Maximun Voltage: 275 Va.c.
-Characteristics input remote Trip/Reclose 1-2
Input not using optocoupler
24 ... 125 Vdc
REC
REC
MT
REC
MT
REC
WARNING: The reclosing sequences marked by are only for motorized circuit breakers with or
without trip coil. I >63 A.
N
Maximun DC Load Breaking
Capacity:
Maximun opening current
Electrical useful life for
AC
loads: No of cycles
MAG
¡ IMPORTANT !
The relay only self-recloses before a trip by earth leakage, short-circuit/overload current fault. The Test (red button) only
verifies the relay trips the protection. It recloses only by manual pressing RESET button.
0 DISABLED
1 2 1 minute 30 minutes
2 2 1 minute 60 minutes
3 2 90 s 30 minutes
4 2 90 s 60 minutes
5 2 3 minutes 30 minutes
6 ... ... ...
7 ... ... ...
8 ... ... ...
0 DISABLED
1 6 8, 16, 30, 59, 115 and 224 s 15 minutes
2 30 20, 40 s and 5 min. to the end 15 minutes
3 8 30 s, 1, 2, 3, 4, 5, 6 and 7 min 15 minutes
4 6 10, 20, 30, 60, 130 and 600 s 15 minutes
5 6 2, 4 y 8 min. to the end 15 minutes
6 7 30 s, 1, 2, 3, 4, 8 and 16 min 30 minutes
7 10 1 min 30 minutes
8 10 90 s 30 minutes
9 8 2, 4 y 6 minutes to the rest 15 minutes
10 10 3 minutes 30 minutes
11 7 2, 4, 8, 16, 32, 32 and 32 minutes 15 minutes
12 31 2, 4 and 6 15 minutes
13 6 8 s 15 minutes
14 ... ... ...
minutes to the rest
MAG
MAG
MAG
MAG
MAG
MAG
MAG
REC
REC
GREEN LED: ON
RED LED: TRIPPED BY FAULT
SCREENS / SETUP
R
RESET button: It reinitiates the operation of the equipment by any event
that tripps it.evento. It indicates the equipment version.
YELLOW LED: Locked by reclosures (fix)
Betwen reclosures (blinking)
- FREQ, ( ) frecuency (Hz)
- LIM,( ), range of values (Id / td)
- SEC. T, ( ),contacts 5-6 [NA/NC]
- TRIP, ( ), breaking element (without trip coil)
- RST.C, ( ), initiates the partials counters.
50
1s, 3A
NO
MA
NO
Default values in SETUP
TEST button: It makes a forced firing to verify the protection.
Button
FREQ
LIM
SEC.T
TRIP
Button
60 Hz
10 s, 30 A
RST.C
Mb
Pulsador PROG
PsI
50 Hz
1 s, 3 A
St
MA
YES
NO
SETUP SETTINGS
A long press in activates the SETUP settings. In this operating
mode by pressing buttons and it shows the submenus and the
setting values to modify . With these
PROG
PROG
PROG new setting values are
validated, the message SAVE is shown by display and exits setting
mode. In case of keypad inactive, it exits setting mode and the message
EXIT is shown by display wihtout changes.
In TRIP (Circuit Breaker), The value is used when the CB don’t need a
trip coil. The value is used when CB needs one.
In SEC.T it defines the working mode of outputs contacts relay 5-6. By
default 5-6 is normally open (St )
(LOCKED SIGNAL)
(See graph)
(See graph)
24... 125 V dc.
4
M203A01-03-18A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Circutor RGU-10 MT and is the answer not in the manual?

Circutor RGU-10 MT Specifications

General IconGeneral
BrandCircutor
ModelRGU-10 MT
CategoryRelays
LanguageEnglish

Related product manuals