ELECTRICAL DATA
URBAN MASTER - URBAN SLAVE
M2 T2 M2-C1 T2-C2
Power supply
1P+N+PE 3P+N+PE 1P+N+PE 3P+N+PE
Input voltage
230V~±10% 400V~±10% 230V~±10% 400V~±10%
Input current
32 A
Frequency
50Hz / 60Hz
Number of sockets
2
Maximum socket Power
7.4 kW 22 kW 7.4 kW 22 kW
Maximum Socket current
32 A
Connectors type
Type 2 Socket Type 1 Cable Type 2 Cable
Charging Mode
Mode 3
Min. cable cross-section
(3)
25 mm
2
Meter
MID Class 1 - EN50470-3
Overcurrent protection
MCB 40A (Curve C)
Safety protection RCD Type A (30 mA) / Type B
(4)
Surge protection
(4)
Transient surge protector IEC 61643-1 (Class II)
URBAN M21, URBAN T21, URBAN M22, URBAN T22, URBAN T22-C, URBAN T24-MIX
M21 T21 M22 T22 T22-C T24-MIX
Power supply
1P+N+PE 3P+N+PE 1P+N+PE 3P+N+PE
Input voltage
230V~± 10% 400V~± 10% 230V~±10% 400V~±10%
Input Current
35 A 67 A
Frequency
50Hz / 60Hz
Number of
sockets
1 2 : Socket A, Socket B
4
(5)
: 2 socket A,
2 socket B
Maximum
socket Power
7.4 kW 22 kW
7.4 kW
(socket A & B)
22 kW
(socket A & B)
22 kW / 3.7 kW
(socket A & B)
Maximum
socket
current
32 A 32 A (socket A & B)
32 A / 16 A
(socket A & B)
Connectors
type
Type 2 Type 2 (socket A & B)
Type 2 / CEE 7/3
(socket A & B)
20
URBAN
Installation Guide