Procedure
Step 1
Verify that the correct fuse panel is installed in the top mounting space.
Step 2
Measure and cut the cables as needed to reach NCS 1001 from the fuse panel.
Step 3
Dress the power according to local practice.
Step 4
Connect the office battery and return cables according to the fuse panel engineering specifications.
Step 5
Insert the DC connector into the DC receptacle on the power supply.
Figure 25: Connecting DC Power
DC Power Cord1
Step 6
Ensure that either the fuse is inserted or the circuit breaker is in the ON position. Verify that the Green LED on the PSU
is on.
37