EasyManua.ls Logo

CleanWater Tech CD1500P - Page 11

Default Icon
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical (continued)
10
Step 1: Mount the 4-20mA controller to a suitable vertical surface according to the installation manual supplied
with the controller.
Step 2: Wire the #22 AWG orange positive(+) lead from the ozone generator to the 4-20mA controller according
to the manual supplied with the controller.
Step 3: Wire the #22 AWG purple negative (-) lead from the ozone generator to the 4-20mA controller according
to the manual supplied with the controller.
Step 4: Complete the required programming and calibration steps as outlined in the installation manual supplied
with the 4-20mA controller.
Step 5: Air Preparation System Power: 120VAC systems only: plug the power cord into main power. 240VAC
systems only: the power cord must be hard wired to the main power source (Black-L1, White-L2/N and Green-Ground).
Notes: The prescribed air flow of the air prep system must be set toatmospheric pressure” prior to use, follow
Step 5 of the ‘Start-up & Calibration' section. Warnings: Failure to calibrate may lead to premature failure of the
air preparation system. Vacuum from the venturi must be interrupted if the air prep system is not “ON;” failure
to do so will damage the air prep system.
External Loop Electrical Interface
Figure 5-1
120 VAC Signal
L1 Power from ORP, PPM,
pump or timer
N
120V
Coil
Interface Relay
External Loop
240 VAC Signal
L1 Power from ORP, PPM,
pump or timer
L2
240V
Coil
Interface Relay
External Loop