INSTALLATION - USER - MAINTENANCE MANUAL
Water-cooled liquid chillers
GB
BRH FF
0011÷0121

Questions and Answers

  • J
    Jared StephensonAug 12, 2025
    Why is my CLIMAVENETA BRH 0071 FF not starting?
    • J
      Jackie FergusonAug 12, 2025
      Your CLIMAVENETA Chiller might not be starting due to several reasons. There could be no voltage, in which case you should check the presence of voltage and safety systems upstream of the appliance. Alternatively, a contactor coil, the HSW12 controller, or the start-up capacitor (if featured) might be faulty, requiring component replacement. Other potential causes include a faulty compressor or reversed phases (for three-phase units).
  • M
    michaelmckinneyAug 16, 2025
    What causes high discharge pressure in CLIMAVENETA BRH 0071 FF?
    • S
      Stephanie FloresAug 16, 2025
      High discharge pressure (greater than 32 bars) in your CLIMAVENETA Chiller can be caused by high outside water temperature. If this occurs, you should check the water temperature. It may also be due to a high utility water inlet temperature.
  • E
    Edward LawrenceAug 19, 2025
    What causes low suction pressure in CLIMAVENETA BRH 0071 FF?
    • R
      Richard SantosAug 20, 2025
      Low suction pressure (less than 4 bars) in a CLIMAVENETA Chiller can stem from several factors. These include a low utility water inlet temperature, a low outside water inlet temperature, or a faulty or blocked thermostatic expansion valve, so you should check these components. It may also be caused by a blocked water filter or a blocked plate heat exchanger.
  • C
    chapmanchristopherAug 23, 2025
    How to fix noise and vibrations in CLIMAVENETA BRH 0071 FF Chiller?
    • J
      Jessica ScottAug 23, 2025
      Noise and vibrations in your CLIMAVENETA Chiller can be caused by contact between metal bodies; you should check for this. Another cause may be loose screws, so tighten them.
  • R
    rellisAug 27, 2025
    Why is the compressor noisy in my CLIMAVENETA BRH 0071 FF Chiller?
    • S
      Steven ReidAug 27, 2025
      A noisy compressor in your CLIMAVENETA Chiller may be caused by liquid returning to the compressor, which you should check. Another possible cause is inadequate fastening.
  • K
    Katherine PatrickAug 31, 2025
    What causes high suction pressure in CLIMAVENETA BRH 0071 FF?
    • N
      Nicholas ReeseAug 31, 2025
      High suction pressure (greater than 20 bars) in your CLIMAVENETA Chiller could be due to a high utility water inlet temperature or a faulty or excessively open thermostatic expansion valve. In such cases, you should check these components.
  • K
    kurtsawyerSep 4, 2025
    What causes low discharge pressure in CLIMAVENETA Chiller?
    • J
      James JacobsSep 4, 2025
      Low discharge pressure (less than 16 bars) in a CLIMAVENETA Chiller can be caused by a low utility water inlet temperature, so you should check this.
  • R
    Richard OrtizSep 7, 2025
    What to do if there is moisture in the refrigerant circuit of CLIMAVENETA Chiller?
    • K
      Kristi MarshallSep 8, 2025
      If there is moisture in the refrigerant circuit of your CLIMAVENETA Chiller (indicated by a yellow flow indicator), you should empty and refill the system.

Summary

INSTALLATION

CHOICE OF INSTALLATION SITE

Guidance on selecting the proper location for unit installation, considering safety distances and access.

POSIZIONAMENTO

Instructions for correctly positioning the unit during installation, including lifting and leveling.

WATER CONNECTIONS

Details on connecting the unit's water circuits and required components like gauges and filters.

CHECKING AND STARTING UP THE UNIT

PREPARING FOR FIRST START UP

Steps to prepare the unit for initial operation or after long shutdowns, ensuring safety and connections.

STARTING UP FOR THE FIRST TIME (after 2 hours)

Detailed procedure for the unit's first-time startup and power-up, including preheating the oil.

ACTIVATING AND DEACTIVATING THE UNIT

Instructions for normal activation and deactivation of the chiller unit, including checks and alarms.

HSW12 FUNCTIONS

DESCRIPTION OF THE BUTTONS AND ASSOCIATED FUNCTIONS

Explanation of individual buttons and their functions on the HSW12 controller for operation and navigation.

DESCRIPTION OF THE BUTTONS - COMBINED ACTION

Details on functions achieved by combining button presses on the HSW12 controller, like programming.

LEDS AND DISPLAY

STATUS AND OPERATING MODE LEDS

Explains the meaning of status and operating mode LEDs on the controller display.

VALUE AND UNIT OF MEASURE LEDS

Describes the LEDs indicating values and units of measure on the controller.

UTILITY LEDS

Details the meaning of utility LEDs indicating component status (compressor, pump, etc.).

OPERATING CHARACTERISTICS

Cooling set point

Defines the factory default cooling set point and hysteresis for the unit.

COMPRESSOR START UP DELAY

Explains features preventing frequent compressor starts, ensuring longevity.

CIRCULATING PUMP

Describes the operation of the circulating pump managed by the electronic board.

WATER FLOW ALARM

Details the water flow alarm system and its management, including safety devices.

ALLARME ANTIGELO

Explains the frost protection function and its parameters to prevent water freezing.

SHUTTING DOWN FOR LONG PERIODS

Procedures for safely shutting down the unit for extended periods and subsequent restart.

SPECIAL MAINTENANCE

CHEMICAL WASHING

Recommendation for chemically flushing the plate heat exchanger every 3 years.

REFRIGERANT GAS CONTENT

Information on refrigerant charge, leaks, and handling procedures for R410A.

CLIMAVENETA BRH 0071 FF Specifications

General IconGeneral
BrandCLIMAVENETA
ModelBRH 0071 FF
CategoryChiller
LanguageEnglish