EasyManua.ls Logo

CLIVET ID2-XY 35M - Page 59

CLIVET ID2-XY 35M
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
Page 59
Model
ID2-XY 70M
Pipe Length (m)
MC2-Y 70M
Cooling 5 10 20 30 40 50
Height
difference
H (m)
Indoor Upper
than Outdoor
25 0.914 0.894 0.874
20 0.944 0.924 0.903 0.883
10 0.975 0.954 0.933 0.912 0.891
5 0.995 0.984 0.963 0.942 0.921 0.900
0 1.000 0.989 0.968 0.947 0.926 0.905
Outdoor Upper
than Indoor
-5 1.000 0.989 0.968 0.947 0.926 0.905
-10 0.989 0.968 0.947 0.926 0.905
-20 0.968 0.947 0.926 0.905
-25 0.947 0.926 0.905
Heating 5 10 20 30 40 50
Height
difference
H (m)
Indoor Upper
than Outdoor
25 0.983 0.977 0.970
20 0.990 0.983 0.977 0.970
10 0.997 0.990 0.983 0.977 0.970
5 1.000 0.997 0.990 0.983 0.977 0.970
0 1.000 0.997 0.990 0.983 0.977 0.970
Outdoor Upper
than Indoor
-5 0.992 0.989 0.982 0.975 0.969 0.962
-10 0.981 0.974 0.968 0.961 0.955
-20 0.966 0.960 0.953 0.947
-25 0.952 0.946 0.939