EasyManua.ls Logo

CLIVET ID2-XY 35M - Page 60

CLIVET ID2-XY 35M
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
Page 60
Model
ID2-XY 105M
Pipe Length (m)
MC2-Y 105M
Cooling 5 15 25 35 50 65
Height
difference
H (m)
Indoor Upper
than Outdoor
30 0.885 0.845 0.805
20 0.921 0.894 0.854 0.813
10 0.958 0.931 0.903 0.862 0.822
5 0.995 0.967 0.940 0.912 0.871 0.830
0 1.000 0.972 0.945 0.917 0.876 0.834
Outdoor Upper
than Indoor
-5 1.000 0.972 0.945 0.917 0.876 0.834
-10 0.972 0.945 0.917 0.876 0.834
-20 0.945 0.917 0.876 0.834
-30 0.917 0.876 0.834
Heating 5 15 25 35 50 65
Height
difference
H (m)
Indoor Upper
than Outdoor
30 0.962 0.943 0.924
20 0.975 0.962 0.943 0.924
10 0.987 0.975 0.962 0.943 0.924
5 1.000 0.987 0.975 0.962 0.943 0.924
0 1.000 0.987 0.975 0.962 0.943 0.924
Outdoor Upper
than Indoor
-5 0.992 0.979 0.967 0.954 0.935 0.917
-10 0.972 0.959 0.947 0.928 0.909
-20 0.951 0.939 0.921 0.902
-30 0.932 0.913 0.895

Related product manuals