5.3 Micro-Switch Introduce:
1
2
ON
1
2
ON
1
2
ON
1
2
ON
SW1
TEL0
24
15
8
EEPROM
DEFAULT
FACTORY
SETTING
FOR ANTI-COLD WIND
A. Micro-switch SW1 is for selection of indoor fan stop temperature (TEL0) when it is in anti-cold wind action in heating
mode.
Range: 24°C, 15°C, 8°C, according to EEROM setting (reserved for special customizing).
T2
Setting fan speed
H
M+
M
L
Super slow
Fan off
TEL0
+16
TEL0
+14
TEL0
+12
TEL0
+10
TEL0
+8
TEL0
+6
TEL0 +1
2
TEL0 +1
0
TEL0 +8
TEL0 +6
TEL0 +4
TEL0
FOR SETTING FAN MOTOR CONTROL
WHEN THERE IS NO DEMAND
1
ON
1
ON
SW2
FAN OFF FAN ON
MODE
FACTORY S ETTING
B. Micro-switch SW2 is for selection of indoor FAN ACTION if room temperature reaches the set point and the
compressor stops.
Range: OFF (in 127s), Keep running.
1
ON
1
ON
FACTORYSETTING
FOR SETTINGAUTO-RESTARTFOR SETTINGAUTO-RESTART
SW3
MODE
AUTO-RESTART
NOTAUTO-RESTART
C. Micro-switch SW3 is for selection of auto-restart function.
Range: Active, inactive
1
2
ON
1
2
ON
1
2
ON
1
2
ON
FACTORY
SETTING
SW5
MODE
MAINMAIN SLAVE
MAIN
NO SLAVE
FOR MAIN-SLAVE SETTING
D. Micro-switch SW5 is for setting the master or slave unit when the unit is in twin connection.
Range: Master no slave (Normal 1 drive 1 connection), Master (2 positions without difference), Slave