M07J40G8-00 21/07/08 page 25
ACCESSIBLE PARAMETERS
PARAMETER MENU STRUCTURE
PARAMETERS
Set
LIST
Thermoreg.
Antifreeze
LIST
Maintenance
LIST
Set - point
LIST
SCHEDULING
Enscheduling
LIST
Configure
LIST
CLOCK SETUP
Clock
LIST
Data
LIST
menu: PARAMETERS – THERMOREG. – SET POINT
DEFAULT values
90 / CEN SecondSetC Secondary cooling Set Point 12
118 / CEN SetCool Cooling Set Point 6.5
272 / CEN SetRecovery NOT USED 35
menu: PARAMETERS – THERMOREG. – MAINTENANCE
114 / CEN SetMantCool Summer maintenance setpoint 15
menu: PARAMETERS - THERMOREG.– ANTIFREEZE
115 / CEN AllFreeze Antifreeze alarm set 4
121 / CEN PreAF Antifreeze pre-alarm set 4.5
261 / CEN SetResist Antifreeze heater set 4
menu: PARAMETERS – SET – UNIT - EVAPORATORS
37 / EVAP SetResist Antifreeze heater set 4
39 / EVAP ALLFreeze Antifreeze alarm set 4
41 / EVAP PreAF Antifreeze pre-alarm set 4.5