pag 38
E 00
Serial faulty - comunicazione tastiera / scheda base Auto.
E 1
Faulty or disconnected water inlet probe Auto
E 2
Faulty or disconnected water outlet probe Auto.
E 3
Faulty or disconnected radiating panel water probe (radiating panel option) Auto.
E 4
Faulty or disconnected coil probe Auto.
E 5
Electric heater output probe Auto.
E 6
Faulty or disconnected external probe Auto.
E 7
Faulty or disconnected pressure transducer Auto.
E 8
Plug-in pressure probe
C 9
Water Reset inlet in short circuit or out of range Auto.
E 10
Faulty or disconnected external RH% probe Auto.
E 11
High pressure MANUAL
E 12
Low pressure Auto.
E 13
Condensing fan and/or compressor thermal switch MANUAL
E 14
Electric heater antifreeze alarm MANUAL
E 17
Pump flow Auto.
E 18
System charged with water MANUAL
E 19
Phase monitor Auto.
E 20
Antifreeze alarm MANUAL
C 21
Antifreeze PREAlarm Auto.
C 22
High pressure PreAlarm Auto.
C 24
Pump change Auto.
E 25
flow alarm C1 Auto.
E 30
Coil frost alarm MANUAL
E 31
Cooling limit alarm (radiating panel option) Auto.
E 32
Water frost alarm (radiating panel option) Auto.
E 33
Incongruent DeltaT alarm MANUAL
C 34
Low pressure pre-alarm Auto.
C / E 35
Inlet water temperature over threshold after cooling / sanitary hot water switching
and vice versa
Auto
C 36
Incongruent sanitary H2O thermostat Auto
1
flashing
Alarm code
Alarm unit hours
2
opened alarm log
short pressure
ALARM
3
The most recent alarm is
visualized
Use the arrow keys to
visualize other alarms
4
To esc
Short pressure
ALARM
5
To RESET
LONG pressure
ALARM
ALARM
STATUS
SET
E 11 2
AL
AR
M
S
TATUS
SET
AL
ARM
STATUS
S
ET
AL
AR
M
S
T
AT
US
SET
AL
AR
M
S
T
AT
US
SET