5547666-CTG-A-0718
160 Johnson Controls Unitary Products
EXTENDED RANGE HEATING DATA
CONDENSING UNIT MODEL NO CH16B4821S
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
AIR TEMP.
ENTERING
INDOOR COIL (°F)
ID CFM
1200 1400 1600
MBH COP KW MBH COP KW MBH COP KW
0
60 26.7 2.66 2.92 28.5 2.76 3.03 32.7 2.87 3.32
70 23.7 2.07 3.35 25.4 2.15 3.47 29.2 2.24 3.81
80 20.9 1.49 3.78 22.3 1.54 3.92 25.6 1.60 4.30
-10
60 21.5 2.52 2.47 23.0 2.62 2.56 26.4 2.72 2.82
70 19.1 1.97 2.84 20.5 2.04 2.94 23.5 2.12 3.23
80 16.8 1.41 3.20 18.0 1.46 3.32 20.6 1.52 3.65
-20
60 16.3 2.89 3.05 30.2 3.19 3.17 34.7 3.39 3.50
70 14.5 2.23 3.46 27.1 2.45 3.60 31.2 2.60 3.96
80 12.7 1.58 3.87 24.0 1.73 4.02 27.6 1.83 4.42
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).