\\Cilaklfs1\shrdata\Masters\Installation Sheets\Master & Premier\MR160P Installation
Sheet.doc
Page 8 of 18
6. Comms Dip-switch settings
6.1 Standard Pump Comms Setting
(Dipswitch SW3)
1-ON
2-OFF
3-ON
4-OFF
These are factory set to the standard setting unless ordered otherwise.eg Gilbarco.
6.2 Gilbarco Pump comms Setting
(Special software and interface board required)
1-OFF
2-ON
3-OFF
4-ON
7. Triac Dip-switches
Important note:
Great care should be taken not to accidentally change the setting of these switches while
working in the Flame-proof box. Operating the unit with these incorrectly set can result in
damage to the C4000 Power Supply or incorrect operation of the triacs.
These switches are set in the factory and should not be changed.
If they are accidentally changed these are the correct settings for Master / Premier Pump
applications.Note: They are 3 position switches
Pump (Motor triac fitted)