101
Connect the devices to the output
sockets one after the other, ensuring
that the current specified for each socket
is not exceeded, and the generator is
not overloaded.
Note
Turn the devices on, one after the other,
using the device switches.
If possible, plug in/switch on devices
with high startup currents first. Only
connect suitable equipment in perfect
condition to the generator.
Switching off
* Turn the devices off, one after the other,
using the device switches.
Note
If possible, switch devices with the
highest current consumption off last.
* Switch the devices off one after the
other.
Note
Ensure the covers of unused sockets
are closed again properly.
Figure 35
* Allow the engine to continue running for
about 2 minutes, so that the generator
cools down.
* Stop the generator.
11.6 Technical characteristics of
8 kVA 400/230 V generator
Generator model . . . . . . GTS-DWG
8/5-2-ZE
Generator type . . . . . . . Synchronous,
internal pole
Generator frame . . . . . . B3/two bearings
Degree of protection . . . IP 54
11. Generator option
Generator characteristics:
Extremely low dynamic internal resistance,
same output voltage whether hot or cold,
no dangerous overvoltage during dynamic
overspeed, small reactive effect from non-
linear or very inductive equipment, trouble-
free operation of equipment with phase
control, no dangerous overvoltage of the
unloaded phases, load current may have
significant DC components
Power system
(IEC 38/50Hz) . . . . . . . . 3-phase AC
400V/230V
Amplified phases . . . . . . 3
Nominal output (0.8 cap/ind)
single-phase . . . . . . . . . 5000VA
3-phase (sym) . . . . . . . . 8000VA
Nominal current
single-phase . . . . . . . . . 21.6A
3-phase (sym) . . . . . . . . 11.5A
Startup current . . . . . . . 4.1 times I
rated
Operating mode . . . . . . S1, continuous
Protective measure . . . . Electrical
isolation, with
equipotential
bonding
conductor in
accordance with
VDE 0100.728
Coolant . . . . . . . . . . . . . Air/externally
ventilated with
own fan, inde-
pendent of
direction of
rotation
Permissible speed range 0 to 4000 rpm
Speed for nominal output
3000 to 4000 rpm
Efficiency at nominal output
at 0.8 ind . . . . . . . . . . . . 0.80
at 1.0 . . . . . . . . . . . . . . . 0.82
Distortion factor . . . . . . . < 5%
Weight . . . . . . . . . . . . . . 53 kg
Overall size . . . . . . . . . . BG132
Overall length . . . . . . . . 426 mm
Generator regulator
Model . . . . . . . . . . . . . . LCAR 3
Connector assignment
Pin Colour Function
1 red F1
2 grey F2
3 violet 1/2 U
4 violet 1/2 V
5 violet 1/2 W
Switchbox
Degree of protection . . . IP 54
Dimensions . . . . . . . . . . 211x311x135
Design . . . . . . . . . . . . . . Front panel type
Fusing . . . . . . . . . . . . . . All poles
L1 . . . B16A
L2 . . . B16A
L3 . . . B16A
N . . . . leading N
Insulation monitoring
Model . . . . . . . . . . . . . . GMW-RISO1.0
Controls . . . . . . . . . . . . . Red test button
Green reset
button
Electronic evaluation system
Model . . . . . . . . . . . . . . LLA1.0x
Power supply . . . . . . . . self-powered
230V
Power loss . . . . . . . . . . . < 15W
Permissible load current 0 – 26.1A
Activation of speed
reduction . . . . . . . . . . . . < about 75 W
Time to reduce speed . . 100 seconds
Outputs
For speed reduction . . . Floating two-way
contact with
neutral position
For pressure reduction . Floating two-way
contact with
neutral position
Max. switching voltage . 60V DC
250V AC
Max. current . . . . . . . . . 7A
Power . . . . . . . . . . . . . . 170W DC
1750VA AC
Min. switching load . . . . 0.1A DC
5V DC
Range switch
Type . . . . . . . . . . . . . . . 4-position
Max. voltage at
switching contacts . . . . . 54V (DC)
Measurement reference
potential . . . . . . . . . . . . N
Generator data
Winding Colour Ins. class Resistance
(at 20°C)/Ω
U-N brown-blue F 0.48
V-N white-blue F 0.48
W-N black-blue F 0.48
1F1-1F2 red-grey H 22.5
(All resistances measured using the 4-wire
R method)