The Salwico MCP-C WP is a manual call point designed for outdoor environments and is compatible with Salwico conventional fire alarm systems. Its robust construction, featuring PC/ABS material and IP67 ingress protection, makes it suitable for harsh conditions. Activating the fire alarm involves pressing the glass, which then cracks. A protective plastic coating on the glass prevents operator injury during activation. The device can be tested using a special key provided with the unit.
The MCP-C WP features a simple connection with terminals for switch function and loop connections. For Servofighter systems, specific connections are provided. An important note for installation is to add an End of Line resistor between terminals 2 and 4 or 6 and 8 (for Servofighter) after the last section unit, as per system specifications.
The device allows for easy glass replacement. To remove the cover, unscrew the four cover fixing screws. Insert a large flat-bladed screwdriver into the slot between the cover and back box, gently twisting until the latches disengage, then pull the cover away. The glass can then be changed following the illustrated steps.
The Salwico 2IP55 is a base designed for all Salwico IP55 detector adapters, enabling the installation of smoke, heat, and flame detectors in harsh environments with an ingress protection of up to IP55. It is compatible with both addressable and conventional fire alarm systems.
The Salwico DOS3 is a low-profile conventional optical smoke detector engineered for optimal smoke response while maintaining strong immunity to false alarms. It incorporates an alarm verification function, requiring two successive pulses before an alarm is triggered. The detector's design ensures high immunity to air velocities, contamination, and EMC, with a protective mesh allowing smoke entry while preventing insects and airborne contaminants. The DOS3 can be mounted on bases suitable for both dry and harsh environments and is compatible with the OD-5 smoke detector.
For information on suitable base plates, refer to the "Base matrix for Salwico units" document. The connection diagram illustrates how to integrate the DOS3 into a fire alarm system, including connections for an external LED and an End of Line resistor for the last unit.
The detector's design, including its protective mesh, helps minimize maintenance by preventing contamination.
The Salwico MCP-C is a manual call point designed for indoor environments and is compatible with Salwico conventional fire alarm systems. Similar to its outdoor counterpart, pressing the glass activates the fire alarm, and a protective plastic coating prevents operator injury. The device can be tested using a special key included in the delivery.
The MCP-C features a straightforward connection with terminals for switch function and loop connections. For Servofighter systems, specific connections are provided. As with the MCP-C WP, an End of Line resistor should be added between terminals 2 and 4 or 6 and 8 (for Servofighter) after the last section unit, as per system specifications.
Glass replacement and cover removal procedures are identical to those for the MCP-C WP, involving unscrewing the cover, gently twisting to disengage latches, and then replacing the glass.
The Salwico AC-IR-3Fq is a triple frequency conventional infrared flame detector, utilizing advanced manufacturing technology to provide superior fire detection. It is designed to detect smokeless combustible liquid and gas fires, as well as smoke-forming open fires involving carbonaceous materials like wood, plastics, and oil products. The fire evaluation process is carried out by a triple Infrared (3Fq) sensor, protected by a sapphire glass filter that blocks radiation below 6.0µm wavelength. The sensor measures hot carbon dioxide in a specific flame wavelength, while B and C sensors simultaneously measure interference radiation in near wavelengths. This technique, combined with intelligent signal processing, microprocessors, and custom algorithms, ensures excellent detection reliability and high immunity to interference radiation and sunlight.
The detector's sensitivity can be set using the 4-way DIP-switch S1, allowing configuration as Conventional or Addressable and presetting the sensitivity threshold (Class 1, 2, or 3). Class 1 is recommended for high sensitivity (up to 27 m), Class 2 for medium (up to 17 m), and Class 3 for low (up to 12 m). For conventional mode, Sw.No.3 and Sw.No.4 should be ON. For addressable mode, they should be OFF. The detector bases compatible are 5200235-00A (Conventional Base) and 5200237-00A (Addressable Base).
For functional testing, use the Salwico IR Test lamp (part no. 001156). Due to the detector's high immunity to unwanted alarms, testing without the IR test lamp is difficult.
The SPB-ADAPT is a base adapter for Salwico IP55 detector bases (part no. 046950 and NS-2IP55 part no. 046900). It replaces older adapters like SPB-1 (part no. 046915) and NS-ADAPT (part no. N1421). This adapter allows smoke, heat, and flame detectors to be connected and is compatible with all Salwico fire alarm systems. For more information on suitable bases, refer to the "Base matrix" document.
The mounting screws should be fitted with the following torque:
The manual provides detailed connection diagrams for various detector types:
Note: Not all detector types have a remote output; refer to the specific detector's data sheet. For loop units with short circuit isolators, consult the data sheet for that unit.