to 2 degrees, the heating system will engage until reaching 70 degrees Fahrenheit.
Cooling Cuto Point: Sets the temperature for the cooling system to turn o past the setpoint.
To adjust, use the up and down arrows and press Set Cool Cuto to confirm the change.
Example: If the Cool Point is set to 68 degrees Fahrenheit, and the Cooling Cuto Point is set to
2 degrees, the cooling system will engage until reaching 66 degrees Fahrenheit.
Stage Minimum O Time (Minutes): Sets the minimum time heating or cooling will remain o
before initiating again. To adjust, use the up and down arrows. The setting takes aect when
you close this box. Example: If while cooling or heating, the temperature does not reach the
designated Cuto Point before the Maximum Run Time is reached, the cooling system will shut
o and not initiate cooling again until the Minimum O Time is reached.
NOTE: Some HVAC systems automatically enforce a minimum o time. In this case,
the heating or cooling will remain o for the higher of the two settings
(Thermostat or HVAC system).
Stage Configuration (Heat 1-2, Cool 1-2, Auxiliary Heat, Emergency Heat)
14
NOTE: Auxiliary heat and emergency heat are for heat pump systems only.
Delta: Sets how many degrees the current temperature will reach beyond the temperature set
point before the stage engages. To adjust, use the up and down arrows. Example: If the Heat
Set Point is 70 degrees Fahrenheit, and the delta is 2 degrees, the heat stage will engage when
the temperature reaches 68 degrees Fahrenheit.
The following settings take aect when you close the page.