CHILLER
MODELS: CH1001-A
Operator’s & Installation Manual
Release Date: August 9, 2002
Publication Number: 620914301
Revision Date: May 6, 2010
Revision: E
Visit the IMI Cornelius web site at www.cornelius.com
for all your Literature needs.

Questions and Answers

  • S
    Sarah WrightAug 11, 2025
    What to do if Cornelius CH1001-A runs continuously but isn't cooling enough?
    • L
      lryanAug 11, 2025
      If your Cornelius Chiller runs continuously but doesn't cool the process water sufficiently, several factors could be responsible. The condenser might be restricted and need cleaning. The unit could be low on refrigerant or have an inefficient compressor, requiring professional service. The chiller might be undersized for the application, in which case you should contact a Cornelius chiller sales representative. Also, a bypass gas valve might be stuck open, necessitating replacement of the solenoid valve.
  • J
    Jonathan WhitneyAug 27, 2025
    How to troubleshoot a Cornelius Chiller that is not operating and the power light is off?
    • L
      Laura KingAug 27, 2025
      If your Cornelius Chiller isn't operating and the power light is off, begin by checking the main disconnect fuses, wiring, and power lead to the unit to ensure there is power. A defective control power switch or a defective control transformer could also be the cause, requiring replacement. Ensure the voltage supplied to the unit is within ±10% of the nameplate rating. Finally, check for a blown fuse (1 Amp) and replace if necessary.
  • L
    lwellsSep 2, 2025
    Why is the pump not operating on my Cornelius CH1001-A, even though the power light is on?
    • R
      rebeccapetersSep 3, 2025
      If the pump on your Cornelius Chiller isn't operating, but the power light is on, it could be due to several reasons. First, check if the line to or from the chiller is restricted and remove any obstructions. Also, inspect the internal or external filter for blockages, removing and cleaning the strainer if necessary. A defective pump contactor could also be the cause, requiring replacement. Lastly, the pump motor or impeller might be damaged, which would necessitate replacement.
  • B
    Brian CampbellNov 18, 2025
    What to do if my Cornelius CH1001-A Chiller doesn't operate and the red safety light is on?
    • Q
      qsolisNov 18, 2025
      If your Cornelius Chiller doesn't operate, but the power light is on, and the red safety light is also on, it indicates a safety condition. This could be due to high pressure; check for dirty condenser fins or obstructions in the chiller air intake, and then press the high-pressure manual reset switch. If the problem persists, contact the Cornelius Service Department. Alternatively, it could be due to low-temperature conditions, ensure adequate flow through the plumbing system or that the process water isn't too cold (below 35° F). Adjust the thermostat setting, check the bypass valve, replace the solenoid valve, or verify proper voltage. A defective thermostat could also be the cause. A low flow condition could also cause this issue, so check for obstructions in the process water line plu...