CH Series Chiller Operator’s & Installation Manual
Publication Number: 91256 - 4 - © 2002-2014, Cornelius Inc.
INSTALLATION INSTRUCTIONS
LOCATION
Locate the chiller indoors in a well ventilated area with ambient temperatures in the range of 65° F to 100° F. Allow a
minimum of six inches of clearance around the chiller for proper air circulation. Avoid hot air discharge from other
equipment or enclosed areas where heat could build up and cause a rise in ambient temperature.
PLUMBING
Follow standard plumbing practices and local codes in making water connections. Piping that is exposed to high
ambient temperatures may need to be insulated to prevent condensation and/or significant liquid heat gain.
ELECTRICAL
All wiring must conform to the National Electric Code and any applicable local codes. The chiller must be:
1. Permanently wired by means of conduit from the junction box on the rear of the chiller cabinet to a properly
fused disconnect of proper amperage or;
2. Wired to a properly rated power cord and plugged into an outlet with appropriate disconnect and amperage
rating.