23. SETTING HEATING ZONE 1
Ref. Display Description Notes Sect.
C o n t r o l : V A L V E
T i m e : 6 3 0 s e c
23.6
Actuator run time
12.
6
Valve and pump LEDs of heating zone 1 blink
N a m e H t g P l a n t 1
- - - - - - - - - -
23.16
Entering name heating zone 1
15.
4
Use + and – to enter letters or numbers
Use
or to position cursor
H e a t i n g P u m p : A U T
D e l a y O f f : 3 0 m i n
23.15
Control plant pump : MAN ; AUT
Delay switching off pump
12.
12
Valve and pump LEDs of heating zone 1 blink
MAN: always On;
AUT: On with times of current programme.
H e a t E m i t t e r s
R A D I A T O R S
23.1
Choice type heat emittters : RADIATORS ; PANELS;
FAN COILS.
12.
1
Valve and pump LEDs of heating zone 1 blink
D e s i g n O u t s i d e
T e m p : 5 . 0 c
23.2
Design outside temp. for compensated control.
See also 24.
2
12.2
Valve and pump LEDs of heating zone 1 blink
23.
3
Design flow temp. for compensated control
12.
2
D e s i g n F l o w
T e m p : 7 0 . 0 c
Valve and pump LEDs of heating zone 1 blink
24. SETTING HEATING ZONE 2
Ref. Display Description Notes Sect.
C o n t r o l : V A L V E
T i m e : 6 3 0 s e c
24.6
Actuator run time
12.
6
Valve and pump LEDs of heating zone 2 blink
H e a t E m i t t e r s
R A D I A T O R S
24.1
Choice type heat emitters: RADIATORS ; PANELS;
FAN COILS.
12.
1
Valve and pump LEDs of heating zone 2 blink
D e s i g n O u t s i d e
T e m p : – 5 . 0 c
24.2
Design outside temp. for compensated control.
See also 23.
2.
12.2
Valve and pump LEDs of heating zone 2 blink
24.
3
Design flow temp. for compensated control
12.
2
D e s i g n F l o w
T e m p : 7 0 . 0 c
Valve and pump LEDs of heating zone 2 blink
C u r v e O r i g i n T O 2 0
F l o w T : 2 0 . 0 c
23.4
Correction heating curve origin
12.
3
Valve and pump LEDs of heating zone 1 blink
F l o w T L i m i t s
M i n : 1 c M a x : 9 9 c
Minimum and maximum limits flow temperature
12.
5
23.5
Valve and pump LEDs of heating zone 1 blink
C u r v e O r i g i n T O 2 0
F L O W T : 2 0 . 0 c
24.4
Correction of heating curve origin
12.
3
Valve and pump LEDs of heating zone 2 blink
F l o w T L i m i t s
M i n : 1 c M a x : 9 9 c
Minimum and maximum limits flow temperature
12.
5
24.5
Valve and pump LEDs of heating zone 2 blink
S t a r t i n e r t i a
M A N U A L 1 . 0 0 h / c
23.8
Optimum start inertia
13.
4
Valve and pump LEDs of heating zone 1 blink
MANUAL = correction of value manually
AUTOMAT = correction of value automatically
O p t S t a r t H o l i d a y
M a x D u r a t : 1 0 . 0 0 h
23.10
Maximum duration optimum start after a holiday
period
13.
6
Valve and pump LEDs of heating zone 1 blink
O p t i m u m S t a r t
B o o s t i n g 3 . 0 c
23.11
Increase in desired ambient temp. during optimum
start period
13.
7
Valve and pump LEDs of heating zone 1 blink
C o o l i n g T i m e
C o n s t a n t 4 8 . 0 0 h
23.12
Used when ambient detector B3 not installed to
calculate decrease in ambient temp.
13.
8
Valve and pump LEDs of heating zone 1 blink
O p t i m u m S t o p
D e c r e a s e T A 0 . 5 c
23.13
Reduction in desired ambient temp. at last event
end occupancy
13.
9
Valve and pump LEDs of heating zone 1 blink
O p t S t a r t N o r m a l
M a x D u r a t : 2 . 0 0 h
23.9
Maximum duration optimum start after period of
24-hour or 7-day operation
13.
5
Valve and pump LEDs of heating zone 1 blink
O p t i m u m S t o p
M a x D u r a t : 1 . 0 0 h
23.14
Maximum duration period optimum stop
13.
10
Valve and pump LEDs of heating zone 1 blink
S t a r t I n e r t i a
M A N U A L 1 . 0 0 h / c
24.8
Optimum start inertia
13.
4
Valve and pump LEDs of heating zone 2 blink
MANUAL = correction of value manually
AUTOMAT = correction of value automatically
O p t S t a r t H o l i d a y
M a x D u ra t : 1 0 . 0 0 h
24.10
Maximum duration optimum start after a holiday
period
13.
6
Valve and pump LEDs of heating zone 2 blink
O p t S t a r t N o r m a l
M a x D u ra t : 2 . 0 0 h
24.9
Maximum duration optimum start after a period of
24-hour or 7-day operation
13.
5
Valve and pump LEDs of heating zone 2 blink
23.
7
12.7
A m b i e n t A u t h o r i t y
P O S I T I V E : + - - - - c
Ambient authority. Variation in + °C flow temp. with
– 1 °C difference in ambient temp.
A m b i e n t A u t h o r i t y
N E G A T I V E : – - - - - c
23.8
Ambient authority. Variation in °C flow temp. with
+ 1 °C difference in ambient temp.
12.
7
23.7
A m b i e n t A u t h o r i t y
N E G A T I V E : – - - - - c
23.8
Ambient authority. Variation in °C flow temp. with
+ 1 °C difference in ambient temp.
12.
7
12.7
A m b i e n t A u t h o r i t y
P O S I T I V E : + - - - - c
Ambient authority. Variation in + °C flow temp. with
– 1 °C difference in ambient temp.