Remote Slab Sensor Crestron CHV-RSS
Ensure that the sensor conduit is vertically centered in the slab below the
surface.
Sensor Conduit position in Slab
Slab
Heating Cables or Pipes
Sensor Conduit
• In small rooms, position the sensor near the center of the floor.
• In larger rooms, ensure that the sensor is at least six feet from
the wall.
• In very large spaces, two sensors may be used to average the
floor temperature.
• The sensor should be placed midway between the heating
elements.
Sensor Position – Top View
Conduit
Sensor
Center of Floor
(or 6 ft from wall
minimum in large
rooms)
Heating Pipe or
Elements
Midway Between
Heating Elements
or Pipes
Floor
4 • Remote Slab Sensor: CHV-RSS Installation Guide – DOC. 6229A