Remote Slab Sensor Crestron CHV-RSS
Ensure that the sensor conduit is vertically centered in the slab below the
surface.
Sensor Conduit position in Slab
Slab
Heating Cables or Pipes
Sensor Conduit
In small rooms, position the sensor near the center of the floor.
In larger rooms, ensure that the sensor is at least six feet from
the wall.
In very large spaces, two sensors may be used to average the
floor temperature.
The sensor should be placed midway between the heating
elements.
Sensor Position – Top View
Conduit
Sensor
Center of Floor
(or 6 ft from wall
minimum in large
rooms)
Heating Pipe or
Elements
Midway Between
Heating Elements
or Pipes
Floor
4 Remote Slab Sensor: CHV-RSS Installation Guide – DOC. 6229A