Curtis 1356/1356P CAN Expansion Module Manual, Rev. A
47
CONFIGURATION PROGRAM MENU
ALLOWABLE
PARAMETER RANGE DESCRIPTION
Nominal 1 3 Sets the nominal voltage, which is used in fault
Voltage
(36V models)
detection.
3 – 7 1 = 12 V.
(80V models)
2 = 24 V.
3 = 36 V.
4 = 48 V.
5 = 60 V.
6 = 72 V.
7 = 80 V.
Preset Hour 0 65535 h Presets hours of the hour meter and resets the minutes
to zero.
Restore Type
1, 2 This parameter is used to select the source of the
parameters when the 1356 /1356P is powered on.
1 = Load parameters from Back-up parameter block.
2 = Load parameters from Normal parameter block.
The default value for this parameter is 2. When it is
programmed to 1, the 1356 /1356P will load all backup
parameters after cycling KSI, and then the Restore Type
value will reset to 2.
7 — PROGRAMMER: PROGRAM MENUS